REMKO GPM User Manual
Page 39

39
Parameter PARAM K
For access to the PARAM K 
parameter, press the key KM 
(Menu) for approximately 8-10 
seconds.
The display shows:
INFO REG
ERR
>>
K1
K2
K3
K4
Press key K4 >> the display shows:
LANG PAR
PARK >>
K1
K2
K3
K4
Press key K3 (PARK); the display 
shows:
<<
PARAM K
1
>>
K1
K2
K3
K4
The value of the adjusted 
parameter appears through key 
K4 and the corresponding 
arrows; K3 indicates the number of 
parameters to be changed [PARM 
K].
Call up the parameters from 1 to 
21 with the keys K1 (back) and 
K4 (forward); the values of the 
adjusted PARAM K parameter can 
be changed with + and – .
To leave the settings menu, 
press the key KM (Menu) for 
approximately 8-10 seconds. 
If no key is pressed for 
approximately 20 seconds, the 
electronic temperature regulation 
automatically leaves the settings 
menu and returns to the operation 
programme.
Parameters REG SAN and FLOW VL
The parameter "REG SAN" is the 
modulation set point of the NTC1 
sensor found on the rear side of 
the unit;
"FLOW VL" is the value measured 
by the sensor.
Adjustment of "REG SAN" (unit 
sensor)
Press key KM (menu); the display 
shows:
HTG SAN
INFO >>
K1
K2
K3
K4
Press key K4; the display shows:
PROG REG
TIME >>
K1
K2
K3
K4
By pressing the key K2 REG you 
arrive at the temperature settings.
Continue with K4 until the 
following appears on the display:
<<
REG
SAN
>>
K1
K2
K3
K4
The set point appears through the 
arrows above key K4.
Adjust the desired temperature 
value with the keys + and – (e.g. 
18 °C). 
Then press key KM in order to 
return to the output menu.
Display of the value of the NTC1 
sensor [param. "FLOW VL"]
In order to display the temperature 
measured by the sensor on the 
rear side of the unit,
press key KM (Menu).
HTG SAN
INFO >>
K1
K2
K3
K4
Press key K3 (INFO); continue with 
key K4 (>>) until the following 
appears on the display:
<<
FLOW VL
>>
K1
K2
K3
K4
The value that appears on the 
display over the arrows above the 
key K4 is the value that has been 
measured by the NTC sensor
found on the rear side of the unit.
Display of output
In order to display the output 
with which the unit is working in 
percent, press key KM (Menu). 
The display shows:
HTG SAN
INFO >>
K1
K2
K3
K4
Press key K3 (INFO); continue with 
key K4 (>>) until the following 
appears on the display:
<<
BURNER
>>
K1
K2
K3
K4
The value on the display 
corresponds to the output in %.
The reference values are: 
Burner at min. output 0%, 
Burner at max. output 100%. 
These values have no connection 
with the PWM value.
Fault display and reset
In case of malfunction, a flashing 
triangle appears on the display 
with the message:
RESET BOILER
>>
K1
K2
K3
K4
By pressing the key K4 the type of 
fault (from 1 to 4) is displayed. 
Then press KM in order to arrive at 
the fault display (flashing triangle). 
Now press key K1 and the 
malfunction is reset (the flashing 
triangle disappears).
Parameter settings of the electronic temperature regulation