Remko gpm – REMKO GPM User Manual
Page 36

36
REMKO GPM
Unit without electronic 
temperature regulation
With replacement of the gas valve, 
the CO
2
and, if applicable, the
offset value must be adjusted.
- Start the burner and bring it to
"high output" after switching 
on the fan by holding the reset 
button on the rear side of the 
unit depressed for 2-3 seconds.
High output mode is shown by a 
single flash of the green LED on 
the front of the unit. 
After approx. two minutes connect 
a flue gas analytical device and 
read the CO
2
value.
Compare this value with the 
information in the table "Gas 
settings" for the type of gas in use.
- If the value lies beyond the
indicated range, use the 
CO
2
regulating screw at the
Venturi tube.
When tightening the adjusting 
screw the gas flow rate is reduced 
and the CO
2
value along with it
When loosening, the CO
2
value
increases.
Then set the burner to "minimum 
output" by pressing the reset 
button again and holding it for 2-3 
seconds. 
The "minimum output" mode is 
displayed by two quick flashes of 
the green LED.
- Wait until the minimum output at 
the burner has stabilised and check 
that the CO
2
value is the same or
slightly below the CO
2
value of
the high flow rate (up to -0.3%).
With deviating values, use the 
offset screw.
To change the values, unscrew the 
metal plug and use the regulating 
screw: 
When loosening, the CO
2
value
decreases.
When tightening, it increases.
After any changes to the offset 
regulation, the CO
2
value at high
output must be checked again 
through the steps indicated above.
After these steps, set the burner to 
"Normal" operation by pressing 
the reset button again and holding 
it for 2-3 seconds.
This mode is displayed through 
the continuous illumination of the 
green LED.
This also happens if the power 
supply of the unit is switched off 
and then on again.
Unit with electronic temperature 
regulation
With replacement of the gas valve, 
the CO
2
and, if applicable, the
offset value must be adjusted.
- Adjust the regulation parameter
of the sensor NTC1 ("REG SAN" 
on the electronic temperature 
regulation) higher than the value 
measured by the sensor NTC1 
("FLOW VL" on the electronic 
temperature regulation).
- Switch on the burner. After
approximately two minutes after 
starting, it goes to its highest 
flow rate. 
Connect a flue gas analytical 
device and read the CO
2
value.
Compare this value with the "Gas 
settings" (page 32) for the type of 
gas in use.
- If the value lies beyond 
the indicated range, use the 
CO
2
regulating screw at the Venturi
tube.
When tightening, the gas flow 
rate is reduced and the CO
2
value
along with it.
When loosening, the CO
2
value
increases.
Then, at minimum output, set the 
burner to a value that lies below 
the measured temperature by 
adjusting the REG SAN value.
- Wait until the minimum output at 
the burner has stabilised and check 
that the CO
2
value is the same or
slightly below the CO
2
value of
the high flow rate (up to -0.3%).
With deviating values, use the 
offset screw.
To change the values, unscrew the 
metal plug and use the regulating 
screw: 
When loosening, the CO
2
value
decreases.
When tightening, it increases.
After any changes to the 
offset regulation, the CO
2
value
at high output must be checked 
again through the steps indicated 
above.
Replacement of the gas valve and CO
2
and offset regulation
If the unit is not set to 
"Normal" operation, the 
control PCB automatically 
resets the unit after 20 
minutes. 
NOTE
