beautypg.com

Remko gpm – REMKO GPM User Manual

Page 26

background image

26

REMKO GPM

Type B23 horizontal

L1 maximum duct length

without endpieces

Ø 80

Ø 100

Model

Metres

GPM15

29

GPM25

29

GPM35

26

GPM55

15

GPM 75

18

Type B23 vertical

L1 maximum duct length

without endpieces

Ø 80

Ø 100

Model

Metres

GPM15

30

GPM25

30

GPM35

29

GPM55

17

GPM 75

20

Installation examples

Gas fireplace type B23

Room-air-dependent combustion
system.

The combustion cycle is not
compact compared to the
environment in which it has been
installed. The combustion air is
taken directly from the installation
space.
The guidance of the flue gas can
take place in two variants:

a) with the aid of horizontal

ductwork (outside wall
installation) straight through the
outside wall, or

b) with a vertical duct through the

roof, if the ceiling is the roof.

With these installation variants,
sufficient ventilation of the
installation space must be ensured
in order to guarantee the correct
supply of combustion air.
This takes place through openings
in the walls of the room. The
dimensions and characteristics
determined in the standards must
be adhered to.
In particular, DVGW-TRGI 2008
Sec. 5.2.2 and TRF Sec. 7.2.2.
should also be observed.

The combustion air supply must be
made from the outside as a basic
rule:

With mechanical suction plants

in the installation space

If over or underpressure can

occur in the installation space

If the unit is installed in

environments with large
amounts of dust

In operations working with

motor vehicles

In this version a protective
grid should be affixed on the
combustion air supply duct
so that the penetration of
solid objects with a diameter
greater than 12 mm is
prevented.

ATTENTION

Protective grate [S] for combustion
air intake

GPM 15 - 55;

Computerised part no.: 228960
GPM 75

Computerised part no.: 229060

L1

Installation height

2.5 - 3.5 m

L

Schematic

side view

L1

Installation height

2.5 - 3.5 m

Schematic

side view

L

Type B23 horizontal through the
outside wall.

Type B23 vertical through the
ceiling.

We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process.