Remko gpm, Commissioning – REMKO GPM User Manual
Page 30

30
REMKO GPM
Combustion analysis
Start the burner and bring it up 
to "high output" after switching 
on the fan by holding the reset 
button on the front side of the unit 
depressed for 2-3 seconds.
High output mode is shown by a 
single flash of the green LED on 
the front side of the unit. 
Make sure that the gas pressure 
at the input to the gas valve 
corresponds to the prescribed 
value; otherwise make 
adjustments.
After approx. two minutes connect 
a flue gas analytical device to the 
flue gas pipe and read the CO
2
value.
Compare this value to the 
information in the table "Gas 
settings" for the type of gas in use.
The initial commissioning may 
only be carried out by a contract 
installation company or the factory 
customer service department.
Carry out the following steps prior 
to the initial commissioning:
1. Inspect all connections and
screw connections of the unit 
and the gas connections for 
leakage integrity.
2. Check all electrical screw and
plug connections within reach.
3. Check the electrical connection
for polarity and the voltage 
supply (230V/1~/50Hz).
4. Check whether the unit is
properly connected to an 
effective grounding system that 
corresponds to the applicable 
safety standards. Only then is 
the electrical safety and function 
of the unit guaranteed.
5. Check whether the electronic
temperature regulation ATR-6 is 
serviceably connected.
The units are delivered pre-
adjusted from the factory 
according to the desired type of 
gas.
A functional inspection of 
the entire unit including 
leakage inspections of all gas-
conveying connections must 
be conducted.
ATTENTION
ATTENTION
Gas lines may never be used 
for the grounding of
electrical equipment!
Commissioning
It must be ensured that a gas 
supply pressure that conforms to 
standards is continuously present 
in accordance with the locally 
available gas type.
The gas of the network must be 
consistent with the gas category to 
which the unit is adjusted.
For commissioning of the burner, 
proceed as follows:
1. Loosen the lock screw in the
pressure tap of the burner. Do 
not unscrew completely!
2. Connect a suitable pressure
measurement device, e.g. 
U-pipe pressure gauge, min. 
resolution 0.1 mbar.
3. Open the gas shut-off devices.
4. Switch on the main/emergency
switch.
5. Set the room temperature
requirement at the electronic 
temperature regulation ATR-6 to 
a higher value than the present 
room temperature.
6. Set the mode selector switch
on the front side of unit to the 
"Heating" position.
7. Set electronic temperature
regulation to "MANUAL 
MODE".
8. Make sure that the heating
symbol illuminates on the 
display of the electronic 
temperature regulation (mode).
9. Set the heat requirement
temperature higher than 
the temperature measured 
by the room thermostat or 
the electronic temperature 
regulation.
The appearance of a small flame 
on the display indicates that the 
burner is switched on.
It is possible that the ignition 
burner does not ignite with the 
initial commissioning, because 
there is still are in the gas line, 
whereby the unit triggers a fault.
The unit must be unlocked and the 
starting procedure repeated.
Installation and maintenance 
work on the unit as well as the 
gas burner may only be carried 
out by authorised qualified 
technicians! 