REMKO GPM User Manual
Page 31

31
If the value lies beyond the 
indicated range, make adjustments 
with the CO
2
regulating screw at
the Venturi tube.
- When tightening, the gas flow
rate is reduced and the CO
2
value along with it
- When loosening, the CO
2
value
increases.
Then set the burner to "minimum 
output" by pressing the reset 
button again and holding it for 2-3 
seconds. 
The "minimum output" mode is 
displayed by two quick flashes of 
the green LED.
Wait until the minimum output at 
the burner has stabilised and check 
that the CO
2
value is the same or
slightly below the CO
2
value of
the high flow rate (up to -0.3%). 
With deviating values, use the 
offset screw. 
To change the values, pull out the 
metal plug and use the regulating 
screw: 
- When loosening, the CO
2
value
is reduced.
- When tightening, it increases.
After any changes to the offset 
regulation the CO
2
value at high
output must be checked again 
through the steps indicated above.
After these steps, set the burner to 
"Normal" operation by pressing 
the reset button again and holding 
it for 2-3 seconds. 
This mode is displayed through 
the continuous illumination of the 
green LED. 
After completion of all steps for 
the initial commissioning, the user 
is instructed in the use of the unit 
and its regulation. 
If the unit is not set to 
"Normal" operation, the 
control PCB automatically 
resets the unit after 20 
minutes. 
NOTE
CO
2
Regulating screw
Pressure tap
Gas input
Offset regulation
Pressure tap
Gas output
Calibrated
Venturi tube
If the unit should not be used 
for extended periods of time, 
the gas cocks must be closed 
and the main switch of the 
unit must be switched off.
ATTENTION
If the unit is not set to "Normal" 
operation, the control PCB 
automatically resets the unit after 
20 minutes.
This also happens if the power 
supply of the unit is switched off 
and then on again.
ATTENTION
The input of the Venturi tube 
may in no case be covered 
with your hands or other 
objects. 
This can lead to flashback of 
the premix burner.
The unit always conducts a 
follow-up ventilation prior to 
switching off the fans.
NOTE
We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process.