REMKO GPM User Manual

Page 35

background image

35

The values that can be
seen and adjusted with
the electronic temperature
regulation are found in the
column

PARAM K

.

NOTE

When replacing the control PCB,
some inspections must be carried
out and some parameters adjusted.

The programming of the
parameters is necessary and
depends on the selected operation
mode.

For each mode of the unit a
corresponding technical description
is included. This is a list of the
standard values programmed
beforehand at the factory.

Please keep this list up to date with
every change carried out on site so
that any replacement PCB can be
programmed accordingly.

- Inspection of the hardware-
configuration of the PCB

Check with electronic temperature
regulation

The bridge NTC/ VAN must be on
NTC and the CR switch on ON,
see figure below [to the inside
edge of the card];

This configuration is necessary
in order to guarantee the proper
function of the NTC1 sensor.

Bridge to NTC

CR switch

on ON

Programming of the parameters

Programming of the parameters
A1 and A2 is mandatory.

These parameters determine the
heat output of the installed fan-
assisted heater.

With replacement PCBs the
parameters A1 and A2 are not pre-
programmed.

The values that must be set are
indicated in the table below
according to unit model.

Model

A1

A2

A3

GPM15

43

58

83

GPM25

58

72

83

GPM35

56

80

80

GPM55

65

93

70

GPM75

75

100

70

Other parameters:

For adjustment of possible
functions of the unit there is a
table on page 38 that contains
all values of the control PCB with
their factory settings, adjustment
range and meaning.

If no electronic temperature
regulation is being used,
please contact the REMKO
customer service department.

ATTENTION

Replacement of the control PCB