The on-site conversion of the gas
type may only be carried out by
authorised, qualified technicians.

Prior to the conversion, the
country-specific requirements must
be fulfilled.
The kit for conversion from natural
gas to liquid gas is described in the
following.

Kit scope of delivery:

Calibrated diaphragm

Ignition flame nozzle

Notice sticker "Unit converted

to..."

After completion of settings,
replace notice sticker "Unit set to
..." with the supplied sticker "Unit
converted to ...".

Proceed as follows for the
conversion:

Disconnect power supply of the

unit at all poles

Carefully replace ignition nozzle

Carefully insert the calibrated

diaphragm between gas valve
and Venturi tube

Re-connect the power supply

of the unit and prepare the unit
to start

Make sure during the ignition

process that no gas emerges at
the copper pipe connection to
the nozzle

If the burner is in operation and
working at high output, check:

1) that the pressure at the input

to the gas valve corresponds
to the prescribed value for the
respective gas type.

2) that the CO

2

content

corresponds to the prescribed
values for the gas type.

If the measured value deviates, it
must be adjusted with the CO

2

regulating screw.

If it is screwed in, the CO

2

value is

reduced.

If it is unscrewed, the CO

2

value is

increased.

Check the leakage integrity of the
gas circuit again.

Gas type liquid gas G30 - G31

Model

GPM15

GPM25

GPM35

GPM55

GPM 75

Ø Ignition nozzle

mm

0.51

0.51

0.51

0.51

0.51

Ø Gas diaphragm

mm

4.5

5.0

5.1

6.5

6.5

Installation of the diaphragm
of model GPM 75

Installation of the diaphragm of
models GPM 15 / 25 / 35 / 55

The fan-assisted heater
supplied for operation with
liquid gas is adjusted for the
gas G31. When operating
with G30 the CO

2

must

be checked and possibly
adjusted.

ATTENTION

We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process.

Adjustment and maintenance
work may only be conducted
by authorised service
technicians.

NOTE

Conversion to liquid gas