Remko gpm, Flue gas connection – REMKO GPM User Manual
Page 24

24
REMKO GPM
Hanging from the ceiling
For hanging the units by means of eyebolts, the Mounting set for ceiling
installation with horizontal air outlet
is available as an accessory item.
Computerised part no.: 228765
.
Vertical air flow
Hanging the units by means of
eyebolts with downward air flow
(installation with vertical air flow).
For this purpose, the Mounting
set for ceiling installation
with
vertical air outlet
is available as
an accessory item. It consists of
eyebolts with special fastening and
an additional fan thermostat.
Computerised part no.:
228766 to GPM 35
Computerised part no.:
228767 starting from GPM 55
We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process.
Additional thermostat for
fan monitoring
The units work with a closed
combustion cycle. The air outlets
are located in front of the heat
exchanger.
The flue gas evacuation and/
or combustion air supply must
be planned and executed in
observance of the respective local
guidelines.
In addition, installation on outside
walls must be coordinated with the
responsible district master sweep.
The classification of the different
installation versions takes place
pursuant to the European Standard
EN 1020 and/or DVGW-TRGI
Directive 2008 and is a component
of the EC authorisation in the
factory-supplied design.
Individually, the units are
classified for the following
versions:
B23/C13/C33/C43/C53/C63
The installation of the flue gas and
supply air duct can take place in
different ways.
e.g. Gas fireplace type B:
The combustion cycle is not
compact compared to the
environment in which it has been
installed.
The combustion air is taken
directly from the installation space.
This version may only be installed
in rooms that have at least one
door or window that can be
opened to the outside and have
a volume of at least 4 m³ per kW
total nominal heat output of the
unit; or a combustion air opening
of at least 150 cm² leading outside
or two openings that have a clear
cross-section of at least 75 cm²
each.
Flue gas connection