Connection variations

1 Outlet on the wall, right
2 Outlet through the wall, right
3 Outlet through the wall, left
4 Outlet on the wall, left

1

2

3

4

Connection variations of
indoor unit

The units are factory filled with
dry nitrogen to monitor for
leaks. The pressurised nitrogen
is released when the union nuts
are loosened.

ATTENTION

Unit installation

The indoor unit is attached by
means of a wall bracket, under
consideration of air discharge side
located in the lower part.

1. Mark the mounting points on

the structurally permissible
building sections according to
the dimensions of the unit.

2. Remove the housing's break

out opening if necessary.

3. Connect the refrigerant

lines, electrical cables and
condensation line to the indoor
unit as described below.

4. Hang the indoor unit onto the

wall bracket by tilting it back
slightly and then by pressing
the bottom part of the unit
against the bracket (figure 5).

5. Check that the unit is level.

Wall bracket
for indoor unit

The wall bracket for the unit must
be attached with suitable screws
and anchors.

Installation

Installation may only be
performed by authorised
specialists.

NOTE

Oil return measures

If the outdoor component is
installed at a higher level than
the indoor unit, suitable oil return
measures must be taken. This is
normally accomplished by creating
a bend in the oil line, installed at
every 2.5 metres of rise.

5 Connecting

Connecting the refrigerant
lines

The on-site connection of the
refrigerant lines is carried out at
the rear of the unit.

It may be necessary to fit
a reducing or extending adapter to
the indoor units. These fittings are
included with the indoor unit as an
accessory kit. Once installed, the
connections should be sealed to
prevent vapour diffusion.

The following instructions describe
the installation of the refrigerant
circuit and the assembly of the
indoor unit and the outdoor
component.

1. The required pipe diameters are

given in the table "Technical
data".

2. Remove the factory-fitted

protective caps and union nuts
on the connections and use
these during installation.

3. Before flanging the refrigerant

lines, ensure that the union nut
is on the pipe.

4. Prepare the refrigerant lines as

shown below
(Page 19, figures 6+7)

.

REMKO ML...DC - ARCTIC

18

Oil return measures

Outdoor component

Oil pump bend

in suction pipe to

outdoor component

1 x every 5.0

metres of rise in the

line

Radius:

min. 50 mm

max. 8/10 m

Indoor unit