Installation inside buildings

Ensure that heat can dissipate
adequately when placing the
outdoor component in cellars,
attics, adjoining rooms or halls
(figure 4)

.

Install an additional fan with
a rated flow comparative to
that of the outdoor component
being installed in the room.
This is used in conjunction with
ventilation ducts to compensate
any pressure losses (figure 4)

Ensure a continuous and
unobstructed air flow from
outside, preferably using
sufficiently large air intakes
placed opposite each
other(figure 4).

Minimum clearances

Observe the minimum clearances
to allow access for maintenance
and repair work and facilitate
optimum air distribution.

ML 226 DC AT
ML 352 DC AT
ML 522 DC AT

A

150 mm

B

700 mm

C

400 mm

D

150 mm

E

200 mm

Comply with any regulations
and conditions affecting the
structure of the building.
If necessary, fit acoustic
installation.

Minimum clearances

E

C

B

A

D

Air intake

Air outlet

Warm air

Cold

Fresh air

Light

well

Outdoor component

Warm air

Light

well

Additional

fan

4 Installation inside buildings

Air intake

Air outlet

All values in mm

1700

Mounting points for wall bracket

ML 226-352 DC IT

ML 522 DC IT

920

45

270

65

65

790

270

65

65

45

90

70

70

40

17