Troubleshooting and customer service

The equipment and components are manufactured using state-of-the-art production methods and tested several
times to verify their correct function. If malfunctions should occur, please check the functions as detailed in the
list below. Please inform your dealer if the unit is still not working correctly after all the functional checks have
been performed!

Fault

Possible cause

Checks

Remedial measures

The unit does not start
or switches itself off
continually

Power outage, undervoltage,

defective mains fuse / main switch

in off position

Are all other electrical installations

functioning correctly?

Check voltage if necessary wait

until turned on again.

Damaged mains cable

Are all other electrical installations

functioning correctly?

Repair by a specialist

Wait time after switching on is

too short

Have approx. 5 minutes

elapsed since the restart?

Schedule longer waiting periods

Working temperature undercut /

exceeded

Are the fans in the indoor unit

and outdoor component working

correctly?

Take into account the temperature

range for the indoor unit and

outdoor component

Electrical surges caused by thunder

storms

Have there been lightning strikes

in the area recently?

Switch off the mains protection

and switch it on again /

Have it inspected by a specialist

Fault in external condensation

pump

Did the pump shut down due to

a fault?

Check and if necessary clean the

pump

The unit does not respond
to the remote control

Transmission distance too far /

receiver affected by interference

Does the indoor unit beep when

pressing a button?

Reduce the distance to less than 6

m or change position

Defective remote control

Is the unit running in manual

mode?

Replace the remote control

Receiver or transmitter unit

exposed to excessive solar

radiation

Does it function correctly in the

shade?

Place the receiver&transmitter unit

in the shade

Electromagnetic fields are

interfering with transmission

Does it function after removing

potential fault sources?

Signal is not transmitted when

interference sources are

operational

Button on remote control jammed

/ two buttons pressed at same

time

Does the “Send” symbol appear

on the display?

Release the button / press only

one button

Batteries in remote control are flat

Have new batteries been inserted?

Is the display incomplete?

Insert new batteries

The unit is running with
reduced or without
cooling or heating output

Filter is unclean / air inlet / outlet

blocked by foreign objects

Have the filters been cleaned?

Clean the filters

Windows and doors open.

Heating/cooling loads increased

Have there been any

constructional /

application-related changes?

Close windows and doors / install

additional units

Neither cooling nor heating mode

has been set up

Is the cooling/heating symbol

activated in the display?

Correct the settings for the unit

Fins on outdoor component

blocked by foreign objects

Is the fan on the outdoor

component running and are the

fins unobstructed?

Check the fan or winter controller,

reduce the air resistance

Leaking refrigerant circuit

Are there signs of frost

on the fins of the indoor unit?

Repair by specialist

Condensation is leaking out

Collection container drainage pipe

blocked / damaged

Is unrestricted condensation

discharge ensured?

Cleaning of drain pipe and

collector reservoir.

Faulty external condensation

pump or float

Is the condensation tray full

and the pump running?

Call out a specialist to replace the

pump

Condensation has collected in the

condensation pipe

Has the condensation pipe been

laid on a slope and is not blocked?

Lay the condensation pipe on a

slope and clean if necessary

Condensation does not drain off

Are the condensation lines

unblocked and laid on a slope? Are

the condensation pump and float

switch functioning correctly?

Install the condensation pipe on a

slope and clean if necessary / is the

float switch or the condensation

pump defective?