Interior unit

The indoor unit is designed for
horizontal wall installation above
doors. However, it can also be
used on the upper wall area can
be used (min. 1.75 m above the
surface of the floor).

Outdoor component

The outdoor component is
designed for horizontal installation
on a base in outdoor areas.
It should be placed on level, flat
and firm surface. The unit should
also be secured against tipping
over. The outdoor component can
be set up outside as well as inside
a building. For external installation,
please observe the following notes
to protect the unit from weather
conditions.

Wall openings

A wall opening of at least
70 mm diameter and 10 mm
slope from the inside to the
outside must be made for each
indoor unit

We recommend that the inside
of the opening is padded or
lined, e.g. using a PVC pipe,
to prevent the lines being
damaged.

After installation, the wall
opening should be closed off
with a suitable sealant. Do not
use materials containing cement
or lime!

Installation material

The indoor unit is fastened using
a wall bracket and 4 threaded screws
(provided by the customer).

The outdoor component is
attached to the wall with 4 screws
and a wall bracket or on a pedestal
secured to the ground.

Minimum clearance to snow

20 cm

Snow

Windbreak

Wind

Lines in the wall throughput

Control line

Condensation line

Injection line

Suction line

PVC tube

Rain

The unit should be at least 10 cm
off the ground when mounted on
the roof or ground. A pedestal is
available as an accessory.

Sun

The condenser on the outdoor
component gives off heat.
Exposure to direct sunlight further
increases the temperature of the
fins and reduces the heat released
by the finned heat exchanger.
The outdoor component should
be installed on to the north
side of the building whenever
possible. If necessary, take
measures to provide sufficient
shade (responsibility of customer).
This can be accomplished with a
small roof. However, the measures
taken should not affect the flow of
warm outlet air.

Wind

If the unit is being installed in
windy areas, ensure that the
warm outlet air discharges in the
main wind direction. If this is not
the case it may be necessary to
install a windbreak (provided by
the customer). Ensure that the
windbreak does not adversely
affect the air supply to the unit.

Snow

The unit should be wall-mounted
in areas of heavy snowfall.

Installation should then be at least
20 cm above the expected level
of snow to prevent snow from
entering the outdoor component.
An optional wall bracket is
available as an accessory.

REMKO ML...DC - ARCTIC