Problem display by blinker code

Installation instructions for qualified personnel

Important notes prior to
installation

Transport the unit in its original
packaging as close as possible
to the installation location.
You avoid transport damages
by doing so.

Check the contents of the
packaging for completeness
and check the unit for visible
transport damage. Report any
damage immediately to your
contractual partner and the
shipping company.

Lift the unit at the corners
and not by the refrigerant or
condensation connections.

The refrigerant pipes (injection
and suction line), valves and
connections must be insulated
against vapour diffusion.
If necessary, also insulate the
condensation pipe.

Select an installation location
which allows air to freely
flow through the inlet and
outlet. (See section "Minimum
clearances").

Do not install the unit in
the immediate vicinity of
devices with intensive thermal
radiation. Installation near
sources of thermal radiation
reduces the output of the unit.

Only open the shut-off valves
of the refrigerant lines after the
installation is complete.

Seal off open refrigerant lines
with suitable caps or adhesive
strips to avoid infiltration of
moisture and never kink or
compress the refrigerant lines.

Avoid unnecessary bends.
You thereby minimize loss of
pressure in the refrigerant lines
and ensure clear return flow of
the compressor oil.

Take special precautions with
regard to the oil return if the
exterior component is located
above the indoor unit.
See section "Oil return flow
measures".

If the basic length of the
refrigerant line exceeds 5
metres, add refrigerant.
The quantity of additional
refrigerant is provided in the
chapter "Add refrigerant".

Only use the union nuts for the
refrigerant pipes included in the
delivery, and remove them only
shortly before connecting the
refrigerant lines.

Make electrical connections in
accordance with the effective
DIN and VDE standards.

Always fasten electric cables
properly to the electrical
terminals. Otherwise a fire
could result.

Display Cause

Required action

E0

EEPROM error

Contact specialty company

E1

Communication error between outdoor component and

indoor unit

Disconnect from mains for 2 min, check wiring

E2

Wiring fault L/N/Pe/S

Check wiring, replace IT circuit board

E3

Vaporiser fan speed too low

Check wiring, check motor voltage

E5

Outdoor temp. sensor / condenser temperature fault /

short-circuited

Check wiring, contact specialty company

E6

air circulation sensor / vaporiser faulty / short-circuited

Check wiring, contact specialty company

P0

IGBT electrical surge protection

Check wiring, check compressor wiring contact spe-

cialty company

P1

Electrical surge / Undervoltage protection

Check voltage on the L/N/S system. Switch off and

turn on again

P2

Excessive compressor temperature protection (Klixon) has
tripped

Check refrigerant quantity, wiring, Klixon

P4

IPM power board safety shutdown

Check wiring, switch off and on again, contact specialty

company