Lighting panel wiring for ge, Latching relay lighting contactors, Component & system wiring 71 – Orion System VCM Component User Manual
Page 71: Relay expansion board, Lighting panel controller

Component & System Wiring
71
FILENAME
DATE:
B. Crews
DESCRIPTION:
PAGE
DRAWN BY:
Using GE Latching Relays
JOB NAME
02/12/04
O-LightingPnl-GE1.CDR
OE310 Lighting Panel Controller Wiring
1
Note:
Set-up, Programming
And Monitoring Of
The Lighting Panel
Controller Requires
The Use Of A
Personal Computer
And PrismSoftware.
1.)24 VAC Must Be Connected So
That All Ground Wires Remain
Common.
3.)All Communication Wiring To Be 18
Ga. Minimum, 2 Conductor Twisted
Pair With Shield. Belden #82760 Or
Equivalent.
4.)It Is Recommended That All
Controllers Address Switches Are
Set Before Installation.
2.)All Wiring To Be In Accordance With
Local And National Electrical Codes
and Specifications.
Local Loop RS-485
Communications To Other
Controllers On The Local
Loop
Ribbon Connector
Relay Expansion Board
Ground
24V
All switches
(1 thru 4)
must be in the
“ON” position
EPROM
RAM
PAL
PIN 1
PIN 1
PIN 1
PIN 1
CPU
+V
+V
1
3
4
5
6
7
8
G
G
2
ANALOG
INPUTS
GND
SIG
+5V
ANALOG
OUTPUTS
A1
A2
G
T
SH
R
GND
24VAC
Lighting Panel Controller
Light Circuit 1
Light Circuit 2
Light Circuit 1
Light Circuit 2
Light Circuit 3
Light Circuit 3
Light Circuit 4
Light Circuit 4
Light Circuit 5
Light Circuit 5
Light Circuit 6
Light Circuit 6
Light Circuit 7
Light Circuit 7
T
SH
R
ON
OFF
24VAC
GE Lighting Relay- Circuit #1
(By Others)
Typical Wiring Shown For Circuit #1
All Other Circuits Are To Be Wired
Identically. Up to 7 Lighting Circuits May
Be Wired To Each Lighting Panel Controller.
K1
R1
R2
R3
R4
R5
R6
R7
R8
K2
K3
K4
K5
K6
K7
Light Sensor
(Optional)
See Note 1
Line Voltage
Line Voltage
16
8
4
2
1
Address Switch Shown Is
Set For Address 1
Address Switch Shown Is
Set For Address 13
Controller
Address Switch
This Switch Must Be
In The ON Position
As Shown
These Switches Should Be
In The OFF Position
As Shown
ADD
ADD
ADD
The Address For Each Controller
Must Be Unique To The Other Controllers
On The Local Loop
Required VA For Transformer
Each Controller = 25VA Max.
Momentary Pushbuttons
(Optional)
Override Circuit #1
Override Circuit #2
Override Circuit #5
Override Circuit #3
Override Circuit #6
Override Circuit #4
Override Circuit #7
Caution: If Lighting Contactor Coil Current Draw Is More Than 2
Amps And/Or Does Not Use A 24VAC Coil, A Pilot Duty Relay
That Has A Current Draw Of Less Than 2 Amps @ 24VAC Must
Be Used To Energize The Lighting Contactor. A Separate
Transformer Rated For The Total Lighting Contactor(s) Or Pilot
Relay Current Draw Must Always Be Used To Power The Circuit.
Note:
All Circuit Board
Contacts Are N.O.
All Contacts Are
Rated For 2 Amps
@ 24VAC Pilot
Duty Only
Do Not Apply Any
Voltage Greater
Than 24VAC
!
!
!
Caution!
Controller Must Have Address Switch Set Between 1 And 60
Lighting Panel Wiring For GE
®
Latching Relay Lighting Contactors