Return air bypass wiring, Component & system wiring 49, Vcm controller wiring detail return air bypass – Orion System VCM Component User Manual
Page 49

Component & System Wiring
49
FILENAME
DATE:
B. Crews
DESCRIPTION:
PAGE
DRAWN BY:
JOB NAME
OVCM-RA-Byp-Wr1A.CDR
1 of 1
03/06/06
VCM Controller Wiring Detail
Return Air Bypass
24
V
A
C
GND
10 VA Minimum Power Required For
Each 2 Slot Expansion Base Board.
20 VA Minimum Power Required For
Each 4 Slot Expansion Base Board
R20
C8
TB2
D3
PWR LD1
24V
AC-IN
GND
GND
TB1
PJ2
+24VDC-OUT
R17
PJ1
R15
Connect To VCM Controller
Connect To Next
Expansion Board
(When Used)
GND
AOUT4
AOUT3
2-10 VDC
2-10 VDC
OE355
-
4
Analog
Output
Board
OE352 or OE353 Expansion Base Board
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-
to-24VAC. Failure to observe polarity will result in damage to one or more
of the boards. Expansion Boards must be wired in such a way that power to
both the expansion boards and the controller are always powered together.
Loss of power to the expansion board will cause the controller to become
inoperative until power is restored to the expansion board.
GND
AOUT1
YS101786
4 AOUT MOD. I/O BD.
CX1
U1
Q1
LM358
R2
U2
R9
D1
R6
D2
R7
D4
D3
R8
TB1
CX2
C3
C1
P1
RV
1
R1
C4
U3
C2
LM358
CX3
AOUT2
AOUT3
AOUT4
Q2
R3
Q4
Q3
R4
R5
Return Air Bypass
Damper Actuator
(2-10 VDC)
Return Air
Damper Actuator
(2-10 VDC)
Belimo Actuator
Wiring Shown.
Consult Factory For
Other Manufacturers
Wiring Instructions
Y1
3
Y1
3
+
2
+
2
COM 1
COM 1
Return Air Bypass Wiring