Component & system wiring 36 – Orion System VCM Component User Manual
Page 36

Component & System Wiring
36
FILENAME
DATE:
B. Crews
DESCRIPTION:
PAGE
DRAWN BY:
JOB NAME
OVCM-Spc-RemSA-Rst-Wr1A.CDR
1 of 1
03/06/06
VCM Controller Wiring Detail
Space Sensor & Remote Supply Air Temp. Reset
Remote Supply Air
Temperature Reset Signal
(By Others)
AIN7
GND
0-5 VDC or 0-10 VDC Signal
GND
Pullup Resistor PU7 Must Be
Removed When Using The
Remote Supply Air Temperature
Signal Input
Reset
Note:
Either The Slide Offset Option For The Space
Temperature Sensor Or The Remote Supply Air
Temperature Reset Signal Option (by Others) May Be
Connected To AIN7 On The VCM Controller. Only
One Option Is Allowed, Not Both.
Note:
When Using 0-10 VDC For The
Remote Signal Source Must
Have (2) 10kOhm Resistors
Wired As Shown. When Using 0-
5 VDC For The Remote Signal
These Resistors are Not
Required And The Signal Can Be
Wired Directly To AIN7 and GND.
Note:
When Using 0-10 VDC For The
Remote Signal Source Must
Have (2) 10kOhm Resistors
Wired As Shown. When Using 0-
5 VDC For The Remote Signal
These Resistors are Not
Required And The Signal Can Be
Wired Directly To AIN7 and GND.
OE210,OE211, OE212 or OE213
Space Temperature Sensor
OVR
OVR
AUX
GND
TEMP
10kOhm
10kOhm
Space Temperature Sensor & Remote Supply Air Reset Wiring