Component & system wiring 66, Warning, Caution – Orion System VCM Component User Manual
Page 66

Component & System Wiring
66
Notes:
1.) All wiring to be in accordance with local and national electrical codes
and specifications.
2.) All modular power/comm cables are to be WattMaster part number
PCC-xx or PCCE-xx cables. All other communication wiring to be 2
conductor twisted pair with shield (Belden #82760 or equivalent).
Comm/Power Cable
Power/Comm
Board Used For Connecting MiniLink PDs Or Previous MiniLink
PD On Network Loop. If This Is The First Power/Comm Board
On The Network Loop, This Power/Comm Cable Connection Is
Not Required. Instead Use The 3 Pole Terminal Block
Communication Connection As Shown Below And Connect
To The CommLink. See Note 2.
From Other
Connect Power/Comm Cables To
Power/Comm
Or MiniLink PDs On The Network Loop Only.
Other
Distribution Board,
Use To Connect CommLink When
This Is the First Power/Comm Board
On The Network Loop. Otherwise No
Connection Is Required. See Note 2.
FILENAME
DATE:
B. Crews
DESCRIPTION:
PAGE
DRAWN BY:
Component Wiring Diagram
JOB NAME
O-Pwr-CommWire1A.CDR
OE365-01 Orion Power/Comm Board
2 of 2
TB2
VA
C
F1
25
4A
24
SHLD
T
R
POWER
LD1
TB1
C1
POWER
&
COMM
DIST
.
BOARD
YS101856
REV
.
0
P5
P4
P3
P1
D1
V1
R1
P2
COMMPIN
POWER&
COMM
OUT
Line Voltage
24VAC
R
SH
T
R
SH
T
R
SH
T
R
SH
T
All Comm Loop Wiring Is
Straight Thru
Network Loop RS-485
192000 Baud
Network Loop RS-485
19200 Baud
4 Amp Slow Blow Fuse
WARNING!
DO NOT GROUND THE 24V TRANSFORMER
THAT IS TO BE USED WITH THE POWER/COMM
BOARDS. GROUNDING OF THE TRANSFORMER
WILL DAMAGE THE POWER/COMM BOARD
AND ALL BOARDS CONNECTED TO IT. A
SEPARATE TRANSFORMER MUST BE USED
FOR EACH POWER/COMM BOARD. NO
EXCEPTIONS. DO NOT CONNECT ANY OTHER
DEVICES TO THE TRANSFORMER USED FOR
THE POWER/COMM BOARD!
CAUTION!
No Local Loop Devices
(VAV/Zone Controllers,
System Manager(s) Etc..)
Can Be Connected To The
Same Power/Comm Board(s)
That Are Used To Supply
Power And Communications
For MinLink PDs On The
Network Loop.
Note:
Diagram Shown Is For Wiring
For Wiring Of Local Loop Devices
Such As VAV/Zone Controllers,
System Manager(s) and Other
Power/Comm Boards On The Local
Loop See Page 1 Of This Drawing
For Wiring .
When
Power/Comm Board Is Used For
Connection Of MiniLink Polling
Devices On The Network Loop.
02/11/004
24VAC Transformer (By Others)
See System Configuration Installation &
Commissioning Section Of This Manual
For Detailed Sizing Information
Power/Comm Board Wiring - When Used For Network Loop Devices