Minilink pd status, Minilink pd confi guration & status screens, Vav/cav/mua operator interface sd 64 – Orion System VAV II Controller v.1 User Manual
Page 64

Zone
Zone
MINILINK PD STATUS
VAV/CAV/MUA Operator Interface SD
64
MiniLink PD Confi guration & Status Screens
Confi guration Screen #4 - Optimal Start
Target Zone
Polling Unit Config
Optimal Start
Target Zone..: XX
[Enter Target Zone]
This is the unit ID of the Zone that you want to be satisfi ed by the normally
scheduled start time. If you enter “-1” into this box, it will average all
zones instead of picking a specifi c zone. If you do not require Optimal
Start, enter “0”. Valid entry is -1 to 58.
Confi guration Screen #5 - Maverick Testing
Polling Unit Config
Maverick Testing
Disabled: YES
Use < Or > To Change
Select YES or NO. Disabling the Maverick Testing allows known troubled
zone(s) to continue voting without causing a Maverick alarm. In other
words, all zones are included in the voting regardless of whether they are
more than four degrees from setpoint.
Confi guration Screens #6-65 - Alarm Polling
Polling Unit Config
Enable Alarm Polling
Unit XX: YES
Use < Or > To Change
Select YES or NO. Enabling Alarm Polling allows any alarm from the
loop to be polled. You must set this for each controller on the loop.
MiniLink PD Status
Status Screen #1 - Schedule Mode, System
Status, and Minutes Left
Polling Device
System Occupied
Venting Mode
XXX Min Left in Mode
Line 2 Current Schedule Mode
Can be System Occupied or System Unoccupied.
Line 3
Currently System Status
Can be Vent Mode, Cooling Mode, or Heat Mode.
Line 4
Minutes Left In Mode
The number of minutes left in the current mode of
operation before it can switch modes. This value is
user-adjustable.
See
Confi guration Screen #3 on
page 63.
Status Screen #2 - Mode Priority, Cool Total,
and Heat Total
Polling Device
No Mode Priority
Cool Total.: XX.XºF
Heat Total.: XX.XºF
Line 2 Mode Priority
Can be Heat Priority or Cool Priority. This is based on
the voting zones and their demand.
Line 3
Cool Total
Total cooling temperature demand from all zones.
Line 4
Heat Total
Total heating temperature demand from all zones.
- CAV II Controller v.1 MUA II Controller v.1 VAV II Controller v.2 CAV II Controller v.2 MUA II Controller v.2 Modular System Manager SD VCB-X VCB-X Controller VCC-X Controller VCB-X Modular Service Tool VCM Controller Operator Interfaces SD VCM-X/RNE Controller VCC-X VCM-X/RNE Controller Operator Interface SD SA E-BUS Controller Modular System Manager SD Quick Start