VAV/ZONE CONTROLLER PROGRAMMING
VAV/CAV/MUA Operator Interface SD
59
Description
Minimum
Default
Maximum
Out of Limits
1 Min
30 Min
300 Min
Setpoint Screen #14 - Day/Night Schedule
XX Box Spts IDXXXX
Day/Night Schedule
Control #: X
0=AHU 1-5=Scheduler
This screen allows you to set the VAV/Zone Controller to operate on a
remote schedule instead of the schedule that is contained in the VCM
Controller. Enter
<0>
to operate on the AHU schedule. Enter
<1-5>
to use an external schedule. A GPC Plus is required for schedules 1-5.
Description
Minimum
Default
Maximum
Schedule Control Number
0
0
1 to 5
Setpoint Screen #15 - Maximum Slide Offset
XX Box Spts IDXXXX
Maximum Slide Offset
Effect on Spt.: XºF
If the Flush Mount Wall Sensor has the optional Setpoint Slide Adjust,
this is the maximum amount you can adjust the heating and cooling
setpoints up or down as the slide is moved from the center position to
its full up or down position.
Description
Minimum
Default
Maximum
Effect on SP
0ºF
0ºF
6ºF
Setpoint Screen #16 - Push-Button Override
Duration
XX Box Spts IDXXXX
Push-Button Override
Duration : X.X Hr
If the Flush Mount Wall Sensor has the optional Push-Button Over-
ride, this is the amount of the VAV/Zone Controller will resume using
its Occupied Setpoints during unoccupied mode. This will generate a
call for the Air Handler to start its fan and provide heating or cooling,
depending on how you confi gure the Air Handler.
Description
Minimum
Default
Maximum
Duration
0.0 Hr
0.0 Hr
8.0 Hr
Setpoint Screen #17 - Maximum EMS Offset
XX Box Spts IDXXXX
Maximum EMS Setpoint
Offset...: XXºF
If the Energy Management System (EMS) is activated, the heat and cool
setpoints can be spread apart by this amount.
Description
Minimum
Default
Maximum
Maximum EMS Setpoint
Offset
0ºF
0ºF
30ºF
Setpoint Screen #18 - Sensor Calibration for
Space Temp and Supply Air Temp
Sensor Calibration
SPC: XXX.Xº XXX.Xº
SAT: XXX.Xº XXX.Xº
[SAT Only if Sensor]
The Thermistor Type III sensor readings can be calibrated. Enter a
Positive value to increase a reading and a Negative value to decrease
a reading.
NOTE: The Supply Air Temperature calibration offset only oper-
ates on the reading when the VAV/Zone Controller has
its own Supply Air Temperature sensor installed on the
AUX2 input. If the supply temperature is received from
a global broadcast, you will need to go to the air handler
to calibrate the temperature reading.
Description
Minimum
Default
Maximum
SPC (Space Temp)
-100ºF
0ºF
+100ºF
SAT (Supply Air)
-100ºF
0ºF
+100ºF
VAV/Zone Setpoint Screens
- CAV II Controller v.1 MUA II Controller v.1 VAV II Controller v.2 CAV II Controller v.2 MUA II Controller v.2 Modular System Manager SD VCB-X VCB-X Controller VCC-X Controller VCB-X Modular Service Tool VCM Controller Operator Interfaces SD VCM-X/RNE Controller VCC-X VCM-X/RNE Controller Operator Interface SD SA E-BUS Controller Modular System Manager SD Quick Start