MUA II CONTROLLER SETPOINTS
VAV/CAV/MUA Operator Interface SD
46
MUA II Setpoint Screens
Setpoint Screen #1 - Supply Air
Temperature Setpoint
MUA II SPTS 0001
Supply Air Temp
Setpoint...: 70ºF
The Supply Air Setpoint is the desired temperature to be delivered by
the MUA II at any time during the Occupied Mode of operation.
Description
Minimum
Default
Maximum
Supply Air Temp
Setpoint
50ºF
70ºF
90ºF
Setpoint Screen #2 - Staging Deadbands
MUA II SPTS 0001
Staging
Deadbands
Cooling.....: 5ºF
Heating.....: 5ºF
The Cooling Deadband added to the Supply Air Setpoint is the Cooling
Mode Setpoint.
When the Outside Air Temperature rises above this setpoint, the MUA
II will go into Cooling Mode. The Heating Deadband is subtracted from
the Supply Air Setpoint to get the Heating Mode Setpoint.
When the Outside Air Temperature drops below this setpoint, the MUA
II will go into Heating Mode.
Description
Minimum
Default
Maximum
Cooling Deadband
2ºF
5ºF
20ºF
Heating Deadband
2ºF
5ºF
20ºF
Setpoint Screen #3 - Unoccupied Deadbands
MUA II SPTS 0001
Unoccupied Deadbands
Cooling.....: 0ºF
Heating.....: 0ºF
During the Unoccupied Mode, these values will be added to the Cool-
ing Setpoint and subtracted from the Heating Setpoint. These settings
are only used if the controller has been confi gured to utilize a Space
Temperature Sensor.
Description
Minimum
Default
Maximum
Unoccupied Cooling Deadband
0ºF
0ºF
30ºF
Unoccupied Heating Deadband
0ºF
0ºF
30ºF
Setpoint Screen #4 - Systems with Reheat -
Dewpoint Control Setpoint
MUA II SPTS 0001
Systems with Re-heat
Dewpoint Control
Setpoint...: 55ºF
The systems capable of Dehumidifi cation will enter this mode of opera-
tion when the Outside Air Dewpoint rises above the Dewpoint Setpoint.
Description
Minimum
Default
Maximum
Dewpoint Setpoint
40ºF
55ºF
80ºF
Setpoint Screen #5 - Enthalpy Staging -
Deadband and Hysteresis
MUA II SPTS 0001
Enthalpy Staging
Deadband....: 5BTU
Hysteresis..: 1.0BTU
The Enthalpy Deadband is the amount of Enthalpy in the Outside Air
needed to activate an extra stage of cooling. The Enthalpy Hysteresis
is used to avoid unnecessary cycling of the Cooling Stages when the
Outside Enthalpy is close to the setpoint.
Description
Minimum
Default
Maximum
Enthalpy Deadband
3 BTU
5 BTU
20 BTU
Enthalpy Hysteresis
0.5 BTU
1.0 BTU
2.5 BTU
Setpoint Screen #6 - Heat Delay During
Dehumidifi cation
MUA II SPTS 0001
Heat Delay During
Dehumidification
Will Occur..: 2 Min
If Heating during Dehumidifi cation is confi gured, this is the amount
of time the Heating call will be delayed after the Dehumidifi cation is
activated.
Description
Minimum
Default
Maximum
Heat Delay
0 Min
2 Min
10 Min
- CAV II Controller v.1 MUA II Controller v.1 VAV II Controller v.2 CAV II Controller v.2 MUA II Controller v.2 Modular System Manager SD VCB-X VCB-X Controller VCC-X Controller VCB-X Modular Service Tool VCM Controller Operator Interfaces SD VCM-X/RNE Controller VCC-X VCM-X/RNE Controller Operator Interface SD SA E-BUS Controller Modular System Manager SD Quick Start