VAV/CAV/MUA Operator Interface SD

MUA II CONTROLLER STATUS

51

MUA II Status Screens

Status

The MUA Controller Status Screens are accessed by pressing the

button on the Modular Service Tool or Modular System

Manager. Enter the correct unit ID number of the MUA Controller
you want to confi gure and press

. Once communication is

established, the *00* message will go away. Then

press

<

>

. You will

then see Status Screen #1. Press

<

>

to scroll through the screens.

NOTE:

If the *00* remains, it indicates a communication failure

to the controller.

Status Screen 1 - HVAC Mode

MUA-II v.2.01 0001

UNOCCUPIED

Vent Mode

07/16/2013 08:00 PM

Line 2 Displays one of the following:

UNOCCUPIED

Remote

Occupied

OCCUPIED

Holiday

Operations

FORCED

OCCUPIED

FORCED

UNOCCUPIED

FORCED

OUTPUT

Line 3 Vent

Mode Cooling

Mode

Heating

Mode

Dehumidifi cation

Line 4

Displays one of the following:

MM/DD/YY HH:MM XX (XX = AM or PM)

Fan Starting Delay and then time will display

xx Left in WarmUp (Number of Minutes Left)

Status Screen 2 - Current Supply Air

Temperature & Supply Air Setpoint

MUA-II v.2.01 0001

Supply Air: XX.XºF
Supply Spt: XX.XºF

Line 2

Current Supply Air Temperature

Line 3

Current Supply Air Setpoint

Status Screen 3 - Current Outdoor Air

Temperature and Cooling & Heating Setpoints

MUA-II v.2.01 0001

Outdoor Air: XX.XºF
Cooling Spt: XX.XºF
Heating Spt: XX.XºF

Line 2 Current Outdoor Air Temperature

Line 3

Cooling Cooling Mode Setpoint

Based on the current Occupied/Unoccupied Mode

of

operation.

Line 4

Current Heating Mode Setpoint

Based on the current Occupied/Unoccupied Mode of

operation.

Status Screen 4 - Current Outdoor Air

Dewpoint, Dewpoint Setpoint & Outdoor RH

MUA-II v.2.01 0001

Dewpoint...: XX.XºF
Dewpoint Sp: XX.XºF

Outdoor RH.: 0.0%

Line 2

Current Outdoor Air Dewpoint

Line 3

Current Dewpoint Setpoint

Line 4

Current Outdoor Humidity

Status Screen 5 - Current Outdoor Air

Enthalpy, Enthalpy Setpoint & Enthalpy

Deadband

MUA-II v.2.01 0001

Enthalpy..: xx.xBTU
Enthalpy Sp: xx.xBTU
Enthalpy DB: xx.xBTU

Line 2

Current Outdoor Air Enthalpy

Line 3

Current Enthalpy Setpoint

Line 4

Current Enthalpy Deadband