Mua ii controller setpoints, Mua ii setpoint screens, Vav/cav/mua operator interface sd – Orion System VAV II Controller v.1 User Manual
Page 47

VAV/CAV/MUA Operator Interface SD
MUA II CONTROLLER SETPOINTS
47
Setpoint Screen #9 - Set Supply Air
Temperature Reset
MUA II SPTS 0001
Set SAT Temp Reset
SPC = 0 Spt = 70
SPC = 0 Rst = 70
A Type III Thermistor Sensor connected to Analog Input #1 can be used
to reset the Supply Air Temperature. This screen allows you to set the
Reset Source Temperatures that the Reset will begin at and the new Reset
Supply Air Temperature range. Determine a desired Space Temperature
you would like to maintain and enter a temperature in the top SPC fi eld
that is 2 degrees higher than your desired Space Temperature. Next,
using the desired Space Temperature you would like to maintain, enter
a temperature in the bottom SPC fi eld that is 2 degrees lower than your
desired Space Temperature. Then enter a value in the “Rst” fi eld on
this screen that is equal to the highest Supply Air Temperature desired.
Whatever Supply Air Temperature you enter for “Rst”, when added
together and divided by 2, should result in a temperature value equal to
your desired Space Temperature.
The “Spt” fi eld value cannot be changed from this screen. This Supply
Air Temperature Setpoint (Spt) must be set from Setpoint Screen #1 on
page 46 and should be set to the lowest Supply Air Temperature that
is desired.
Supply Air Temperature Reset Example:
*Desired Space Temperature is 70°F
Space Temperature (SPC) = 72°F SAT Setpoint (Spt) = 55°F
Space Temperature (SPC) = 68°F SAT Setpoint (Rst) = 85°F
Description
Minimum
Default
Maximum
Minimum Range
40ºF
0ºF
100ºF
Maximum Range
40ºF
0ºF
100ºF
Reset
SAT Spt
SAT Spt
Spt + 50ºF
MUA II Setpoint Screens
Setpoint Screen #7 - Alarm Limits
MUA II SPTS 0001
Alarm Limits
Hi SAT Limit: 150ºF
Lo SAT Limit: 0ºF
If the Supply Air Temperature ever rises above the High SAT Limit or
drops below the Low SAT Limit for a user-defi ned period of time, an
alarm is generated.
Description
Minimum
Default
Maximum
High SAT Limit
50ºF
150ºF
150ºF
Low SAT Limit
0ºF
0ºF
70ºF
Setpoint Screen #8 - Supply Air Alarm
MUA II SPTS 0001
Supply Air Alarms If
Out Of Range For
30 Min
This is the amount of time the Supply Air Temperature must be outside
either the High or Low SAT Limit Setpoint before it generates an alarm.
Description
Minimum
Default
Maximum
Supply Air Alarms If
Out of Range For X
Minutes
0 Min
30 Min
300 Min
- CAV II Controller v.1 MUA II Controller v.1 VAV II Controller v.2 CAV II Controller v.2 MUA II Controller v.2 Modular System Manager SD VCB-X VCB-X Controller VCC-X Controller VCB-X Modular Service Tool VCM Controller Operator Interfaces SD VCM-X/RNE Controller VCC-X VCM-X/RNE Controller Operator Interface SD SA E-BUS Controller Modular System Manager SD Quick Start