Vav/zone controller status, Vav/zone status screens – Orion System VAV II Controller v.1 User Manual
Page 60

Zone
Zone
VAV/ZONE CONTROLLER STATUS
VAV/CAV/MUA Operator Interface SD
60
VAV/Zone Status
Status Screen #1 - Mode of Operation
XX Box v4.01 IDXXXX
Occupied Mode
Vent Mode
Belongs to Group # 1
Line 2
Unoccupied Mode
Occupied
Mode
Override
Mode
Override
Pending*
Damper
Calibration
Group
Override
Line 3 OFF Mode
Vent
Mode
Cooling
Mode
Heating
Mode
Sensor
Fail
Mode**
Line 4 Belongs to Group # xx
No
Group
Affi liation
* Not displayed when using a Digital Room Sensor.
** Displays for either a temperature sensor failure or an airfl ow
sensor failure.
Status Screen #2 - Zone Temperature and
Cooling/ Heating Setpoints
XX Box v4.01 IDXXXX
Zone Temp..: XX.XºF
Cooling Spt: XX.XºF
Heating Spt: XX.XºF
Line 2
Current Zone Temperature
Line 3
Currently active Cooling Setpoint based on the current
Occupied / Unoccupied mode of operation.
Line 4 Currently active Heating Setpoint based on the current
Occupied / Unoccupied mode of operation.
Status Screen #3 - Slide Offset & H/C Demand
XX Box v4.01 IDXXXX
Slide Offset: XXºF
H/C Demand.: XX.XºF
Line 2
If the optional Setpoint Slide Adjust is installed on the
Flush Mount Wall Sensor, this line will display the
current
amount
the
Slide Offset is affecting the
Heating and Cooling Setpoints.
Line 3 Current
Heating or Cooling Demand in the Zone
based on the current Heating and Cooling Setpoints
when compared to the current Zone Temperature.
Line 4
Blank
Status Screen #4 - Supply Air Temperature &
Box Air Temperature
XX Box v4.01 IDXXXX
Supply Air: XX.XºF
Box Air..: XX.XºF
Line 2
Current Supply Air Temperature received via
broadcast from the DX Air Handler or from the Box
Controller’s own installed Box Air Temperature Sensor
connected to the AUX input of the VAV/Zone
Controller
board.
Line 3
Current Box Air Temperature
If you have confi gured the VCM Controller
to broadcast the Supply Air Temperature to the VAV/
Zone Controller and don’t have a Box Air Temperature
Sensor attached to the AUX input on the VAV/Zone
Controller board, this line will display the Supply Air
Temperature the same as line 2.
If you have a Box Air Temperature Sensor attached to
the AUX input on the VAV/Zone Controller board, this
line will display the Box Air Temperature at the
location where the Box Air Temperature Sensor is
installed.
Line 4
Blank
VAV/Zone Status Screens
- CAV II Controller v.1 MUA II Controller v.1 VAV II Controller v.2 CAV II Controller v.2 MUA II Controller v.2 Modular System Manager SD VCB-X VCB-X Controller VCC-X Controller VCB-X Modular Service Tool VCM Controller Operator Interfaces SD VCM-X/RNE Controller VCC-X VCM-X/RNE Controller Operator Interface SD SA E-BUS Controller Modular System Manager SD Quick Start