9 product specifications, 1 technical data, Product specifications – Nortec ME Control User Manual
Page 73: Technical data, 9product specifications
73
Product specifications
9
Product specifications
9.1
Technical data
Nortec ME Control
Supply voltage control unit
100...240 VAC/50...60 Hz
Supply voltage circulation pumps
24 Vdc/50...60 Hz
Power consumption
1)
< 278 W (5 stages, no options fitted)
Control signals
0...5 VDC
1...5 VDC
0..10 VDC
2...10 VDC
0...16 VDC
3.2...16 VDC
0..20 mA
4..20 mA
On/Off (via volt-free contact)
Control accuracy
Control accuracy depends on air conditions, control
distance, water quality and on the number of On/Off
cycles
Max. admissible matric face velocity
3.5 m/s (689 fpm)
4.5 m/s (886 fpm) with droplet separator
Water supply
ø15mm (0.625") compression fitting
Water drain (outside diameter)
ø 54 mm (2.125") - Tank /
ø 28 mm (1.125") - Hydraulic module
Admissible water supply pressure
2...5 bar (29...72.5 psi)
Admissible water temperature
5...20 °C (41...68 °F)
Water quality
Tap water, softened or fully demineralised water with a
max. of 100 cfu/ml
Admissible operating air temperature
10...60 °C (50...140 °F)
Admissible ambient temperature (Control unit)
1...40 °C (33.8...104 °F)
Admissible ambient humidity (Control unit)
max. 75 %rh
Degree of protection of Control unit
IP21
Degree of protection of Hydraulic module
IP42
Conformity
CE marking
Fire classification of evaporative media
glass fibre media: A2-S2,-D0 (UL Class 1)
polyester media: DIN EN 53438 Class F1
1)
Power consumption depending on the number of vertical evaporative cassettes banks and the options fitted