Fault elimination

Code

Message

Information

Warning

Fault

Possible causes

Remedy

–––

E32

Demand Snsr

Demand signal failed, Nortec ME Control automatically stopped operation.

Note: If – at any time – the reading of the demand signal is correct again, the system

will continue with normal operation.
Sensor not connected.

Correctly connect sensor.

Incorrect sensor configuration.

Correctly configure sensor.

Sensor defective.

Replace Sensor.

–––

E44

Water Temp

Water supply temperature is too high, Nortec ME Control changed to “Fill Cycle”

mode dilution. The fault message must be reset after elimination of malfunction.
Standing Water in inlet system.

Check water supply system.

Insufficient thermal insulation of inlet

pipework.

Insulate supply water pipe.

Water temperature limit set too low.

Check/adjust water temperature limit.

Temperature sensor of conductivity sen-

sor configured incorrectly.

Contact your Nortec representative.

–––

E45

Water Condu

Water supply conductivity is too high, Nortec ME Control changed to “Fill Cycle”

mode dilution. The fault message must be reset after elimination of malfunction.
Water treatment defective/needs service. Check/service water treatment system.
Conductivity limit set too low.

Check/adjust Conductivity limit.

Conductivity sensor configured incor-

rectly.

Contact your Nortec representative.

Conductivity sensor defective.

Replace conductivity sensor.

–––

E46

Water Outlet

Tank drain timeout. The Nortec ME Control stopped operation as the tank could

not be drained within a preset time.

Note: If – at any time – the drain level is reached again, the system will continue

with normal operation.
Drain pump blocked/defective.

Check/replace drain pump.

Drain piping or drain trap clogged.

Check/clean drain piping and drain trap.

Level sensor stucked or short circuited. Check/replace level sensor.
Backpressure in drain pipe.

Check drain pipe venting.

–––

E47

Level Sensor

Water level sensor signal failed. The Nortec ME Control stopped operation.

Note: If – at any time – the reading of the level sensor is correct again, the system

will continue with normal operation.
Level sensor not connected.

Correctly connect level sensor.

Level sensor defective.

Replace level sensor.

–––

E48

Water Temp Snsr Water temperature sensor signal failed, Nortec ME Control changed to “Fill Cycle”

mode dilution. The fault message must be reset after elimination of malfunction.
Water temperature sensor not connected. Correctly connect water temperature

sensor.

Incorrect water temperature sensor con-

figuration.

Correctly configure water temperature

sensor.

Water temperature sensor defective.

Replace water temperature sensor.

W49

–––

Matrix Wash

Over

After installation of new evaporative cassettes a wash over procedure needs to

be carried out. The wash over is mandatory for evaporative cassettes with glass

fibre as evaporator media.
Nortec ME Control is commissioned

first time.

Evaporative cassettes matrix must be

washed over with the Matrix wash over

function in service submenu.