Operating the Nortec ME control software

5.4.5 Communication settings – “Communication” submenu

In the “Communication” submenu you determine the parameters for the communication.

Modbus Parameters

Modbus: With this setting you can activate (“On”) or deactivate (“Off”)

communication via a Modbus network.
Factory setting:

Off

Options:

Off or On

The following parameters appear only if the Modbus function is activated.

Modbus Address: With this setting you determine the Modbus ad-

dress for the adiabatic air humidification system Nortec ME for the

communication via a Modbus network.
Factory setting:

10

Setting range:

1 ... 247

Parity: With this setting you set the parity bit for the data transfer.
Factory setting:

Even

Options:

None, Even or Odd

Baudrate: With this setting you set the Baudrate for the data transfer.
Factory setting:

9600

Options:

9600, 19200, 39400, 115200

BMS Timeout: With this setting you set the timeout time for the data

transfer.
Factory setting:

300 Seconds

Setting range:

0 ... 300 Seconds

Indication: With this setting you determine whether only maintenance

messages (“Service”) or all Warning messages (“Warning”) are outputted

via the service relay of the remote operating and fault indication board.
Factory setting:

Service

Options:

Service or Warning

Safety Chain Indication: With this setting you determine whether an Fault

(“On”) or a Warning (“Off”) is triggered when the external safety chain is

open.
Factory setting:

Off

Options:

Off or On

Remote Fault Board