5 communication settings – “communication” submenu, Communication settings – “communication” submenu – Nortec ME Control User Manual
Page 39
39
Operating the Nortec ME control software
5.4.5 Communication settings – “Communication” submenu
In the “Communication” submenu you determine the parameters for the communication.
Modbus Parameters
–
Modbus: With this setting you can activate (“On”) or deactivate (“Off”)
communication via a Modbus network.
Factory setting:
Off
Options:
Off or On
The following parameters appear only if the Modbus function is activated.
–
Modbus Address: With this setting you determine the Modbus ad-
dress for the adiabatic air humidification system Nortec ME for the
communication via a Modbus network.
Factory setting:
10
Setting range:
1 ... 247
–
Parity: With this setting you set the parity bit for the data transfer.
Factory setting:
Even
Options:
None, Even or Odd
–
Baudrate: With this setting you set the Baudrate for the data transfer.
Factory setting:
9600
Options:
9600, 19200, 39400, 115200
–
BMS Timeout: With this setting you set the timeout time for the data
transfer.
Factory setting:
300 Seconds
Setting range:
0 ... 300 Seconds
–
Indication: With this setting you determine whether only maintenance
messages (“Service”) or all Warning messages (“Warning”) are outputted
via the service relay of the remote operating and fault indication board.
Factory setting:
Service
Options:
Service or Warning
–
Safety Chain Indication: With this setting you determine whether an Fault
(“On”) or a Warning (“Off”) is triggered when the external safety chain is
open.
Factory setting:
Off
Options:
Off or On
Remote Fault Board