23

Operation

4.5

Notes on operation

4.5.1 Important notes on operation

– For hygiene reasons the supply valve opens in standby mode

every 12 hours for approximately

20 seconds in order to flush water supply line.

– If no demand is present for more than 23 hours the tank will be drained.

4.5.2 Remote operating and fault indication

The relays on the remote operating and fault indication board indicate the following operating system

status:

Activated

remote indication relay

When?

“Error”

An error is present, operation is stopped or further operation is possible for a limited period

of time only.

“Service”

One of the maintenance counter has elapsed. The corresponding maintenance must be

performed.

“Running”

Demand present/system is humidifying/cooling

“Unit on”

The humidification system is switched on and under voltage

4.5.3 Recommended regular checks during operation

During operation the Nortec ME Control has to be checked periodically in accordance with the table below.

Operations Checks

Daily

Weekly

Monthly

Quarterly

Monitor humidity/temperature control

Check for any low humidity/temperature concerns

Check any alarms on BMS

Visible check for:

– Units switched on with no fault lights

– No water leakage (air on and air off side)

– No water flow to drain (water may flow to drain during

drain cycle and when unit losses humidity demand)

– system components for correct fixing and any da-

mage

– electric installation for any damage.

All UV bulbs are active (with water level), if applicable

Matrix media is saturated (relative to demand signal)

Condition of tanks and air on matrix is clean

Inspect and determine replacement frequency of se-

diment filter

Add DisifinXL chemical (1 sachet per 2 m (6.6 ft) width

of tank)