Nortec ME Control User Manual

Page 37

background image

37

Operating the Nortec ME control software

Setpoint: with this setting you set the humidity setpoint in %rh (if System

Mode is set to “Humidifying”) or the temperature setpoint in °C or °F (if

System Mode is set to “Cooling”).

Note: this setting appears only if the Control Mode is set to “RH P” or

“RH PI”.
Factory setting:

40 % or 20 °C (68 °F)

Options:

0 ... 95 % or 5 ... 40 °C (41... 104 °F)

P-Band Channel 1 / P-Band Channel 2: with this setting you set the pro-

portional range of channel 1 in %rh (if System Mode is set to humidifying)

or of channel 2 in °C or °F (if System Mode is set to cooling).

Note: this setting appears only if the Control Mode is set to “RH P” or

“RH PI”.
Factory setting:

15 %rh or 10 °C (50 °F)

Options:

6 ... 65 %rh or 1.0 ... 50.0 °C (34 ... 122 °F)

Integral time Channel 1 / Integral time Channel 2: with this setting you

set the integral time of channel 1 (if System Mode is set to humidifying)

or channel 2 (if System Mode is set to cooling) in minutes.

Note: this setting appears only if the Control Mode is set to “RH PI”.
Factory setting:

5 minutes

Options:

1 ... 60 minutes

PI Control Parameters

Stage switching

Threshold 1: With this setting you determine the set point at which the

pump of stage 1 will switch on or off in % of the demand signal.
Factory setting:

5 %

Options:

1 ... 99 %

Threshold 2: With this setting you determine the set point at which the

pump of stage 2 will switch on or off in % of the demand signal.
Factory setting:

20 %

Options:

1 ... 99 %

Threshold 3: With this setting you determine the set point at which the

pump of stage 3 will switch on or off in % of the demand signal.
Factory setting:

40 %

Options:

1 ... 99 %

Threshold 4: With this setting you determine the set point at which the

pump of stage 4 will switch on or off in % of the demand signal.
Factory setting:

60 %

Options:

1 ... 99 %

Threshold 5: With this setting you determine the set point at which the

pump of stage 5 will switch on or off in % of the demand signal.
Factory setting:

80 %

Options:

1 ... 99 %