Nortec ME Control User Manual
Page 53
53
Maintenance
Operations
Minor
Service
Complete
System Service
Replace all feed hose
–––
Yes
Check distribution headers
Yes
Yes
Clean distribution headers
–––
Yes
Clean pumps
–––
Yes
Clean front section of tank
Yes
Yes
Clean internal of hydraulic module (use soft cloth only)
Yes
Yes
Check operation of level float and conductivity sensor (if applic able)
Yes
Yes
Clean level float and conductivity sensor
–––
Yes
Check droplet separator (if applicable) and evaporator cassettes in suit-
able condition
Yes
Yes
Lightly brush evaporator cassettes if necessary, replace if heavily soiled
–––
Yes
Remove evaporator cassettes and clean all sections of tank and frame
structure
–––
Yes
Check and secure frame structure and seal
–––
Yes
Run unit and check for correct water level
Yes
Yes
Check all media for full saturation
Yes
Yes
Check drain pump operation and correct flow
Yes
Yes
Check operation of all distribution pumps
Yes
Yes
Measure flow rates to distribution headers
–––
Yes
Check water temperature and conductivity is within calibration
Yes
Yes
Check and secure all electrical connections
Yes
Yes
Check overall installation for leaks and damage
Yes
Yes
Check software settings
Yes
Yes
Check operation of submerged UV lamps
Yes
Yes
Replace UV kits
–––
Yes
Check any options as per relevant documentation
Yes
Yes
Complete disinfection as described in this manual
Yes
Yes
Check safety interlock and humidity/temperature control devices
–––
Yes
Check air velocity at face of evaporative cassettes matrix
–––
Yes
Reset all appropriate maintenance counters
Yes
Yes
Update service log book
Yes
Yes
Add DISIFIN XL disinfection sachet(s) to tank
Yes
Yes