5 consumables guide, 6 health and safety requirements, Consumables guide – Nortec ME Control User Manual

Page 55: Health and safety requirements

background image

55

Maintenance

6.5

Consumables guide

Common consumables

Description

Standard Frequency (month)

DISIFIN XL

1

Disinfection chemical (sourced locally)

6

Descaling chemical (sourced locally)

as required

Inlet flow restrictor

24

Distribution header feed hose

24

Evaporative matrix cassette

– Wholesome mains water

– RO water

36 - 60

60 - 84 +

Option consumables

Description

Standard Frequency (month)

PureFlo Ag+ sediment filter

6

PureFlo Ag+ antimicrobial filter

12

UV bulb kit

12

Contact your Nortec distributor for consumables list/order codes.
To help us ensure that the correct spares parts are sent, please confirm your unit serial and model

number with your order.

6.6

Health and safety requirements

In accordance with local regulations, users must take water samples for Legionella analysis. Samples

should be taken from the same places as described in chapter 6.7 – Routine water sampling and testing,

and the analysis carried out by an accredited laboratory which is part of an appropriately certified Legi-

onella testing scheme. In the event that the Legionella content exceeds 10

2

cfu/l, the humidifier should

be switched off and specialist advice sought regarding its disinfection.
1. If biofilm (a slimy or gel-like deposit when wet, which might be dry and crisp in a dry system) is found

during any inspection of the humidifier or water system, the humidifier MUST be switched off and

not put back into operation until the system has been taken apart, scrubbed and thoroughly cleaned

with a suitable biocide with biofilm penetrating qualities such as 50 ppm chlorine dioxide solution.

This work should only be carried out by fully trained specialist organisations or individuals.

2. The

control unit of the Nortec ME Control must be left powered on to allow automatic flushing

and cleaning cycles to occur. If the control unit

Nortec ME

Control is powered off for prolonged

periods, water stagnation might occur and contamination result, so the system, including any stor-

age tanks or vessels should be drained and left dry. Before putting the system back into service, the

water pipework supplying the

Nortec ME Control

should be purged carefully, avoiding the creation

of aerosols by splashing, and a water sample should be taken to ensure cleanliness. In the event

that the humidifier pipework contains any residual water or has remained damp, and the temperature

exceeded 20 °C (68°F), the

Nortec ME Control

should be disinfected using an appropriate solution.

Contact your Nortec representative for advice on water sampling and analysis, disinfection of systems,

service and maintenance.