Nortec ME Control User Manual
Page 44
44 Operating the Nortec ME control software
5.5.2.1 Input diagnostic functions – “Input Diagnostics” submenu
The following input values can be viewed after accessing the “Input Diagnostics” submenu.
Note: the input values can be accessed and viewed too, via the “Service Info” selection field in the
standard operating display.
Control
–
Humidity control: Actual demand signal in %
–
Temperature control: Temperature of area being controlled.
–
Safety Chain: Actual status of the safety chain (“Open”= Safety chain
open, “Closed”= Safety chain closed)
–
Enable: Actual status of the external enable switch, if present (“Off”=
switch open, “On”= switch closed).
ME Conditions
The ME Conditions section shows operating parameters of options, if installed:
–
Incoming Air Temperature: Actual air temperature of the incoming air in
°C or °F if optional duct temperature sensor is installed.
–
Water Temperature: Actual temperature of the water in the tank in °C or
°F if optional temperature sensor is installed.
–
Conductivity: Actual conductivity of the water in the tank in µS/cm if
optional conductivity sensor is installed.
Level Floats
–
Level: Actual level (1 to 6) in the tank of the evaporative module captured
by the level sensor.
–
Dosing Pump Level Float: Actual level (“Empty”= Tank is empty or
“OK”=Level in the tank is OK) in the liquid tank of the optional system for
enhancing polyester media water absorbtion.