beautypg.com

Nortec ME Control User Manual

Page 44

background image

44 Operating the Nortec ME control software

5.5.2.1 Input diagnostic functions – “Input Diagnostics” submenu

The following input values can be viewed after accessing the “Input Diagnostics” submenu.

Note: the input values can be accessed and viewed too, via the “Service Info” selection field in the

standard operating display.

Control

Humidity control: Actual demand signal in %

Temperature control: Temperature of area being controlled.

Safety Chain: Actual status of the safety chain (“Open”= Safety chain

open, “Closed”= Safety chain closed)

Enable: Actual status of the external enable switch, if present (“Off”=

switch open, “On”= switch closed).

ME Conditions

The ME Conditions section shows operating parameters of options, if installed:

Incoming Air Temperature: Actual air temperature of the incoming air in

°C or °F if optional duct temperature sensor is installed.

Water Temperature: Actual temperature of the water in the tank in °C or

°F if optional temperature sensor is installed.

Conductivity: Actual conductivity of the water in the tank in µS/cm if

optional conductivity sensor is installed.

Level Floats

Level: Actual level (1 to 6) in the tank of the evaporative module captured

by the level sensor.

Dosing Pump Level Float: Actual level (“Empty”= Tank is empty or

“OK”=Level in the tank is OK) in the liquid tank of the optional system for

enhancing polyester media water absorbtion.