beautypg.com

2 malfunction list, Malfunction list – Nortec ME Control User Manual

Page 63

background image

63

Fault elimination

7.2

Malfunction list

Important! Most operational malfunctions are not caused by faulty equipment but rather by improper

installation or disregarding of planning guidelines. Therefore, a complete fault diagnosis always involves

a thorough examination of the entire system. Often, the installation of the evaporative module has not

been properly executed, or the fault lies with the humidity/temperature control system.

Code

Message

Information

Warning

Fault

Possible causes

Remedy

–––

E18

Air Temp Snsr

Nortec ME Control stopped operation as the incoming temperature signal of the

optional anti freeze protection has failed.

Note: If – at any time – the temperature signal reading is correct again, the system

will continue with normal operation.
Sensor wiring broken or sensor defective Check wiring, replace sensor if necessary
Sensor not connected

Correctly connect sensor to driver board

–––

E19

Freeze Prot

The ME stopped operating as the temperature of the incoming air fell below the

preset limit of the optional anti freeze protection.

Note: If – at any time – the air temperature of the incoming air rises above the limit

value again, the system will continue with normal operation.
Temperature too low for safe operation

of the Nortec ME Control

No remedy

Temperature limit set wrong

Contact your Nortec representative.

W20

E20

Safety Chain

The Nortec ME Control stopped operating as an external device opened the safety

chain. E.g. ventilation Interlock, safety humidistat, etc..

Note: If – at any time – the safety chain is closed again, the system will continue

with normal operation.

Note: depending on

the configuration

either Warning or

Fault is indicated

Ventilation interlock open.

If applicable, check/turn on

ventilation system.

Air flow monitor triggered.

Check ventilator/filter of the

ventilation system.

Safety humidistat triggered.

Wait. If applicable, check

safety humidistat

W21

–––

High Water

Water overflow detected. Current operation status not affected.

Note: If – at any time – the normal operating water level is reached, the system will

continue with normal operation.
Inlet solenoid valve blocked in open

position or defective.

Check/replace inlet solenoid valve.

Gravity drain solenoid valve blocked in

closed position.

Check/replace gravity drain solenoid

valve.

Drain piping/drain trap clogged.

Check/Clean drain piping and drain trap.

Backpressure in drain trap.

Check drain trap venting to duct.

Assisted drain function not activated.

Contact your Nortec representative.