beautypg.com

3 control settings – “control settings” submenu, Control settings – “control settings” submenu – Nortec ME Control User Manual

Page 36

background image

36 Operating the Nortec ME control software

5.4.3 Control settings – “Control Settings” submenu

In the “Control Settings” submenu you determine the control settings for the Nortec ME Control. The

control settings available depend on the selected signal source and the control mode.

Basic

Source: with this setting you determine whether the control signal comes

from an analogue source (signal of a humidity sensor or demand signal

from an external humidity controller) or via Modbus.
Factory setting:

Analog

Options:

Analog or Modbus

System Mode: with this setting you determine whether the Nortec ME

Control is configured as an air humidifier (“Humidifying”) or as an air cooler

(“Cooling”).
Factory setting:

Humidifying

Options:

Humidifying (configured as air humidifier)

Cooling (configured as air cooler)

Control Mode: with this setting you determine the type of controller used

with the Nortec ME Control.
Factory setting:

Demand

Options:

On/Off (external On/Off humidistat)

Demand (external continuous controller)

RH P (internal P controller)

RH PI (internal PI controller)

Signal type Channel 1 / Signal type Channel 2: with this setting you

determine the control signal type for Channel 1 (if System Mode is set to

humidifying) or Channel 2 (if System Mode is set to cooling).

Note: this setting appears only if signal source is set to “Analog” and

Control Mode is set to “Demand”, “RH P” or “RH PI”.
Factory setting:

0-10 V

Options:

0-5V, 1-5V, 0-10V, 2-10V, 0-20V, 0-16V, 3.2-16V,

0-20mA, 4-20mA

Temperature Min: with this setting you determine the minimum tempera-

ture of the measuring range of the temperature sensor used.

Note: this setting appears only if System Mode is set to “Cooling” and

Control Mode is set to “RH P” or “RH PI”.
Factory setting:

0.0 °C (32 °F)

Setting range:

–50.0 ... +100 °C (–58 ... 212 °F)

Temperature Max: with this setting you determine the maximum tem-

perature of the measuring range of the temperature sensor used.

Note: This setting appears only if signal source is set to “Analog” and

control mode is set to “Demand”, “RH P” or “RH PI”.
Factory setting:

5

0.0 °C (122 °F)

Setting range:

–50.0 ... +100 °C (–58 ... 212 °F)