beautypg.com

Options and accessories, Mh specifications – Nortec MH Series User Manual

Page 9

background image

Introduction | 6

Options and Accessories

Nortec provides a complete line of options and accessories for every humidification application.
The following options and accessories are available and may have been delivered with your
MHTC humidifier/cooler. Refer to the installation instructions that came with the accessories
for their proper installation and operation.

Table 2: Options and Accessories

Option / Accessory

Used For

Mist Eliminator

Removing water droplets that have been picked up by the air
stream as it flows through the evaporative media.

Conductivity Sensor

Measuring water conductivity in the MHTC Reflow reservoir for
improved water management.

Water Filters

Removing foreign particles from water supplied to the MH.

Water Pressure Regulators

Reducing supply line water pressure supplied to the MHTC Flow
and MHB.

Digital or Analog Control Humidistats

Controlling the output of the humidifier based on sensed RH (can
be mounted in the space being humidified or in the duct).

Digital RH Transducers

Communicating RH in a space or duct to the humidifier

Digital or Analog High Limit Humidistats

Preventing over humidification in a duct by shutting down or
throttling down the humidifier when duct RH gets high.

Air Proving Switches

Insuring humidification only occurs when air is moving in a duct.

Nortec LINKS XPS (MHTC Only)

Connecting the humidifier to a building management interface.
hardware allows control of the humidifier via BACnet, Lonworks,
Johnson N2, or Modbus.

MH Specifications

Table 3: MH Specifications

MHB Flow

MHTC Flow

MHTC Reflow

Voltage

120 vac / 60 hz

120 vac / 60 hz

120 vac / 60 hz

Control signals

VDC 0-10

VDC 0-5, 1-5, 0-10,

2-10, 0-16, 3.2-16

mA 0-20, 4-20

VDC 0-5, 1-5, 0-10,

2-10, 0-16, 3.2-16

mA 0-20, 4-20

Max No. of Stages

3 3 3

Water supply

3/4 in. BPP, 1/2 in.

NPT adapter provided

1/2 in/ FPT

3/4 in. BPP, 1/2 in.

NPT adapter provided

Water drain

2 in. (50.8 mm) OD

tube

2 in. (50.8 mm) OD

tube

2 in (50.8 mm) ID

hose

Control accuracy

Depends on air conditions, number of stages, and control setup

Allowable water supply pressure

30-80 psi (2-5.5 Bar)

Allowable water temperature

41-104ºf (5-40ºc)

Water quality

Tap water, reverse osmosis, softened or fully demineralized water.

Note: Ultrapure DI water not recommended on MHB or Flow Systems.

Max. allowable velocity through media

1100 fpm (5.5 m/s) with mist eliminator.

Pressure drop

Typically 0.44 IWC (250 Pa) @ 500 fpm (2.5 m/s) and 90% RH

Ambient conditions (control unit)

34 -104ºF (1- 40ºC) Max 75% RH

Max. allowable air temp. through media

120 ºF (48 ºC)

Fire classification of evaporative media

UL 900 Class 1 USA, ULC-S111-07 Class 2 Canada