Required maintenance – Nortec MH Series User Manual
Page 63
Maintenance and Servicing | 60
Required Maintenance
MHB Service Reminder
The MHB controller includes a service reminder which will shut down the MHB after 800 hours
of operation. At that time the LCD display inside the control box will display the message shown
in Figure 46: MHB Service Reminder. When the service reminder occurs the media must be
inspected and replaced if it is heavily soiled and all the maintenance indicated in Maintenance
Schedule on page 62 must be performed. Nortec is not responsible for any damages resulting
from, or attributed to not performing required maintenance. (see Manufacturer’s Warranty).
After the maintenance has been performed the service reminder must be reset by
simultaneously pressing / holding button 1 and 4 for three seconds.
Figure 46: MHB Service Reminder
Warning
If the Nortec MH Series is insufficiently maintained microbials which can cause illness, may
grow in the media boxes, the mist eliminator, and the tank and may affect the air passing
through the MH duct unit. Maintenance must be performed as specified.
Caution: Servicing
Poorly maintained humidifiers / coolers can endanger health of building occupants. If
the MH is not properly maintained microbials may grow in it. If carried by air passing
through the humidifier the germs can cause illness.
The MH must be serviced in the intervals described in the maintenance section of this
manual. Humidification boxes and mist eliminator media must be replaced after their
service life has elapsed.
Caution:
All maintenance work must be carried out by qualified and trained personnel.
Power to the MHTC/MHB should always be turned off using the dedicated external
disconnect before removing the cover of the hydraulic unit or opening the control box.
The instructions and details for maintenance work must be followed as described. Only
use original NORTEC spare parts to replace faulty parts.