Plumbing – Nortec MH Series User Manual
Page 25
Installation | 22
Plumbing
General
All water supply and drain line connections must be installed in accordance with local
plumbing codes.
Install water shut off valve and union before humidifier to facilitate servicing.
Insure drain line and overflow line are min 1.25 in. (32 mm) ID. to provide draining.
High hardness supply water will require increased maintenance and more frequent
replacement of evaporative media.
Unit damage caused by water quality outside of the specified ranges is not covered under
warranty.
Note:
Supply untreated potable water, reverse osmosis water, fully demineralised water or
partly softened water. Do not treat water with corrosion inhibitors, disinfectants or other
chemicals.
If fully demineralised water is used then use plastic or stainless steel components for
all plumbing connections.
Flush water lines thoroughly before connecting to the hydraulic unit.