beautypg.com

Nortec digital controls – Nortec MH Series User Manual

Page 44

background image

41 | Start Up

Startup Information Screen

Displays the setting of the Inlet Flush and Softstart
parameters. Inlet flush On = flush tank for 60 seconds on
startu. Softstart On = cycle staging valves 10 sec. On / 10 sec.
Off for first 5 minutes of operation.


UV Module Screen

Displays if the UV light is set to turn on.




Nortec Digital Controls

Nortec provides optional On/Off, Modulating, or Transducer digital humidity controls. Figure 40
and Figure 41 show the function and meaning of the Digital Control’s display and buttons. Wall
controls and the duct mounted On/Off controls come with a built in humidity sensor. The
modulating control for duct installation consists of a display and a remote sensor for duct
mounting.














Figure 40: Modulating and On/Off Digital Control Operation

Output signal is shown on

modulating controller

proportional to the demand.

State of On/Off humidistat

Setpoint (RH%)

Humidity (RH %)

Indicates the

humidistat is on.

A half moon

indicates it is off.

Snowflake indicates the

setpoint is being

overridden by outdoor

temperature.

Option button accesses

sensor calibration.
See troubleshooting

Increase / Decrease Setpoint

Power button turns

off the humidiistat if

pressed for 2 seconds