beautypg.com

Remote relay board wiring – Nortec MH Series User Manual

Page 36

background image

33 | Installation

Remote Relay Board Wiring

The MHTC (not MHB) remote relay board includes 4 relays that can provide remote status
indication. The remote relay board is located as shown in Figure 36: Remote Relay Board
Wiring. The PCB with the relays includes markings which indicate the function of each terminal
on the board. The relays indicate the following status;
1 Unit On – The normally open relay is closed when the humidifier has power and the On/Off

switch is set to on.

2 Steam – The normally open relay is closed when the control board activates at least one

staging valve and water is being evaporated from the evaporative media.

3 Service – The relay can be wired to open (NC) or close (NO) when a warning is displayed on

the MHTC display and the yellow service LED is illuminated.

4 Error – The relay can be wired to open (NC) or close (NO) when a fault is detected by the

MHTC controls.






















Figure 36: Remote Relay Board Wiring

S

team

U

n

it

O

N

Erro

r

Se

rv

ic

e

NO

CO

M

NO

CO

M

NO

CO

M

NC

NO

CO

M

NC

Note:
MHTC units with Nortec Links XPS have the Links XPS board installed in place of the

remote relay board.