Repair Section

85

(5) Evacuation (repeat)

1) Close the valve of the refrigerant cylinder. Then

remove the charging hose (green) from the

refrigerant cylinder, and connect it to the

refrigerant recovery machine.

< NOTE >

Keep the high-pressure valve and the low-

pressure valve of the gauge manifold closed.

2) Using the procedure under “Evacuation”,

evacuate the system until the high-pressure

gauge indicates 30 inHg (100 kPa) or larger. (For

15 minutes or more.)

3) After evacuation is complete, close the high and

the low pressure valves of the gauge manifold.

CAUTION

Make sure to evacuate the system twice or

more using the repetitive vacuum method.

Evacuate the system an additional time on

rainy or humid days.

I002227

LO

Closed

HI

Open

LO

Closed

HI

Closed

Valve Setting

30 inHg (100 k Pa) or larger

High-Pressure Valve

High-Pressure Gauge

Gauge

High-Pressure

Side Tube

Vacuum Pump

(in Operation)

Low-Pressure

Valve