beautypg.com

84 (4) checking for gas leaks, Warning – MovinCool CM25 Service Manual User Manual

Page 84

background image

Repair Section

84

(4) Checking for gas leaks

1) Remove the charging hose (green) from the

vacuum pump, and connect the hose to the

refrigerant cylinder (R-410A).

2) Loosen the nut on the gauge manifold side of the

charging hose (green).

3) Open the valve of the refrigerant cylinder and

perform air purging in the charging hose (green).

Then tighten the nut.

4) Open the high-pressure valve of the gauge

manifold. Charge the system with refrigerant until

the high-pressure gauge indicates 57 psi (390

kPa). After charging is complete, close the high-

pressure valve.

5) Open the valve of the refrigerant cylinder and

perform air purging in the charging hose (green).

Then tighten the nut.

6) Check carefully for gas leaks inside the

refrigerant system using the gas leak tester.

7) Repair any leak.

WARNING

Any repair on a charged system should be

performed by a licensed professional only.

WARNING

Before checking for gas leaks, fully confirm

that there is nothing flammable in the area

to cause an explosion or fire. Contact of

refrigerant with an open fire generates

toxic gas.

I001901

Open The Valve

of Refrigerant

Cylinder

to Process Tube Fitting

Charging Hose

(Green)

Refrigerant Cylinder R-410A

Red

LO

Closed

HI

Closed

Valve Setting

Air Purging

I002228

LO

Closed

HI

Open

LO

Closed

HI

Closed

Refrigerant Cylinder R-410A

Valve Setting

Gauge Reading

57 psi

(390 k Pa)

Open High-Pressure

Valve

High-Pressure

Side Tube

Low-Pressure

Valve (Closed)

Process Tube Fitting

Refrigerant

Cylinder

Valve

(Open)

This manual is related to the following products: