Repair Section

52

LCD

displays

self-

diagnostic

codes.

HP

HP

4

Operating outside of the

operating temperature

range.

Check environmental condition. Do not

operate the unit outside the operating

condition range. (See page 9.)

RESET the controller

*1

.

Insufficient air volume.

Clean air filter.

RESET the controller

*1

.

Check ducting of intake and exhaust air, and

make sure there are no objects preventing air

flow.

RESET the controller

*1

.

Loose high-pressure

switch connection.

Reconnect the high-pressure switch and

check the connection.

RESET the controller

*1

.

Defective high-pressure

switch (short or open).

Replace high-pressure switch.

RESET the controller

*1

.

Refrigerant is over

charged.

Charge correct amount of refrigerant.

(See page 86.)

RESET the controller

*1

.

E01

E01

2

Defective RTS1

thermistor (short or

open).

Replace the WMC.

E02

E02

2

Loose RTS2 thermistor

connection.

Reconnect the RTS2 thermistor and check

the connection.

RESET the controller

*1

.

Defective RTS2

thermistor (short or

open).

Replace RTS2 thermistor.

RESET the controller

*1

.

E03

E03

2

Loose ODS thermistor

connection.

Reconnect the ODS thermistor and check

the connection.

RESET the controller

*1

.

Defective ODS thermistor

(short or open).

Replace ODS thermistor.

RESET the controller

*1

.

E04

E04

2

Loose CTS1 thermistor

connection.

Reconnect the CTS1 thermistor and check

the connection.

RESET the controller

*1

.

Defective CTS1

thermistor (short or

open).

Replace CTS1 thermistor.

RESET the controller

*1

.

Condition

Check Area

Possible Cause

Remedy

Unit does

not

operate.

Self-Diagnostic

Codes

(WMC)

Buzzer

Pattern

User

Mode

Service

Mode

*1 : To RESET the controller, press RESET button, then press ON/OFF button.