6.2 Self-Diagnostic Codes
• Self-diagnostic codes are displayed on the WMC and indicate by LED on the relay board under
the following conditions.
• LED on the relay board indicates self-diagnostic codes for the MWT under the following
conditions.
Self-Diagnostic
Code
Cause
Alarm
Pattern
Relay Board
LED (Red)
Warning
Signal
Output
Detection Contents
User
Mode
Service
Mode
1
2
3
4
5
6
AL
AL
Fire alarm input
1
ON
When receiving fire alarm
signal input.
PU
PU
Condensation overflow
(Internal drain pump)
3
When drain pan float switch
is OFF continuously for 60
seconds.
E07
E07
Condensation overflow
(Optional condensate
pump)
3
When optional drain pan float
switch is OFF continuously
for 60 seconds.
HP
HP
High-pressure signal
detected
-
OFF
When high-pressure switch is
activated 2 times in 24 hours
from first detection.
ON
When high-pressure switch is
activated 3-7 times in 24
hours from first detection.
High-pressure
protection activated
4
When high-pressure switch is
OFF eight times.
E01
E01
WMC room thermistor
(RTS1) failure
2
When an abnormality is
detected.
E02
E02
Evaporator inlet air
thermistor (RTS2) failure
E03
E03
Condenser inlet air
thermistor (ODS) failure
E04
E04
Condenser thermistor
(CTS1) failure
E05
E05
Evaporator pipe inlet
thermistor (CTS2) failure
E06
E06
Evaporator pipe outlet
thermistor (CTS3) failure
E08
E08
WMC communication
error
4
When a communication error
between the relay board and
WMC continues for at least
10 seconds.