Repair Section

44

6.2 Self-Diagnostic Codes

• Self-diagnostic codes are displayed on the WMC and indicate by LED on the relay board under

the following conditions.

• LED on the relay board indicates self-diagnostic codes for the MWT under the following

conditions.

Self-Diagnostic

Code

Cause

Alarm

Pattern

Relay Board

LED (Red)

Warning

Signal

Output

Detection Contents

User

Mode

Service

Mode

1

2

3

4

5

6

AL

AL

Fire alarm input

1

ON

When receiving fire alarm

signal input.

PU

PU

Condensation overflow

(Internal drain pump)

3

When drain pan float switch

is OFF continuously for 60

seconds.

E07

E07

Condensation overflow

(Optional condensate

pump)

3

When optional drain pan float

switch is OFF continuously

for 60 seconds.

HP

HP

High-pressure signal

detected

-

OFF

When high-pressure switch is

activated 2 times in 24 hours

from first detection.

ON

When high-pressure switch is

activated 3-7 times in 24

hours from first detection.

High-pressure

protection activated

4

When high-pressure switch is

OFF eight times.

E01

E01

WMC room thermistor

(RTS1) failure

2

When an abnormality is

detected.

E02

E02

Evaporator inlet air

thermistor (RTS2) failure

E03

E03

Condenser inlet air

thermistor (ODS) failure

E04

E04

Condenser thermistor

(CTS1) failure

E05

E05

Evaporator pipe inlet

thermistor (CTS2) failure

E06

E06

Evaporator pipe outlet

thermistor (CTS3) failure

E08

E08

WMC communication

error

4

When a communication error

between the relay board and

WMC continues for at least

10 seconds.