6.10 Inspection of Compressor

(1) Compressor motor

• Measure resistance across the terminals of the

compressor motor. (All terminals must be

disconnected from the unit.)

• Between terminals {at 68°F (20°C)}

- U-V Approx. 0.64 ohm

- V-W Approx. 0.64

ohm

- W-U Approx. 0.64 ohm

• If the measured resistance is not equal to these

standard values, replace the compressor.

(2) Overload relay

• Check for continuity across two terminals of the

overload relay. At normal temperature, there

should be continuity across the terminals.

Specifications:

- OFF (Open contact): 248°F (120°C)

- ON (Closed circuit): 203°F (95°C)

• If there is no continuity across the terminals,

replace the overload relay.

I003180

V

W

U

I001701