Repair Section

48

Alarm clear method

• Self-diagnostic codes are not displayed for the MWT. To identify the cause, check the LED on

the relay board and refer to the charts on page 44 to 46.

Self-Diagnostic

Code

Cause

Alarm Clear Method

User

Mode

Service

Mode

Wall Mounted Controller (WMC) Millivolt Wall Thermostat (MWT)

AL

AL

Fire alarm input

Press RESET button.

Reset the power from the circuit

breaker.

PU

PU

Condensation overflow (Internal

drain pump)

E07

E07

Condensation overflow

(Optional condensate pump)

HP

HP

High-pressure signal detected

Alarm clears automatically.

Alarm clears automatically.

High-pressure protection

activated

Press RESET button.

Reset the power from the circuit

breaker.

E01

E01

WMC room thermistor (RTS1)

failure

E02

E02

Evaporator inlet air thermistor

(RTS2) failure

E03

E03

Condenser inlet air thermistor

(ODS) failure

E04

E04

Condenser thermistor (CTS1)

failure

E05

E05

Evaporator pipe inlet thermistor

(CTS2) failure

E06

E06

Evaporator pipe outlet

thermistor (CTS3) failure

E08

E08

WMC communication error

E09

E09

Evaporator fan motor locked

E10

E10

Condenser fan motor locked

OL

OL

Compressor overload

E11

E11

STI module communication error

E12

E14

Compressor over current

E15

Compressor lock failure

E16

Compressor phase interruption

abnormality

E17

Motor position detection

abnormality