MovinCool CM25 Service Manual User Manual
Page 48

Repair Section
48
Alarm clear method
• Self-diagnostic codes are not displayed for the MWT. To identify the cause, check the LED on
the relay board and refer to the charts on page 44 to 46.
Self-Diagnostic
Code
Cause
Alarm Clear Method
User
Mode
Service
Mode
Wall Mounted Controller (WMC) Millivolt Wall Thermostat (MWT)
AL
AL
Fire alarm input
Press RESET button.
Reset the power from the circuit
breaker.
PU
PU
Condensation overflow (Internal
drain pump)
E07
E07
Condensation overflow
(Optional condensate pump)
HP
HP
High-pressure signal detected
Alarm clears automatically.
Alarm clears automatically.
High-pressure protection
activated
Press RESET button.
Reset the power from the circuit
breaker.
E01
E01
WMC room thermistor (RTS1)
failure
E02
E02
Evaporator inlet air thermistor
(RTS2) failure
E03
E03
Condenser inlet air thermistor
(ODS) failure
E04
E04
Condenser thermistor (CTS1)
failure
E05
E05
Evaporator pipe inlet thermistor
(CTS2) failure
E06
E06
Evaporator pipe outlet
thermistor (CTS3) failure
E08
E08
WMC communication error
E09
E09
Evaporator fan motor locked
E10
E10
Condenser fan motor locked
OL
OL
Compressor overload
E11
E11
STI module communication error
E12
E14
Compressor over current
E15
Compressor lock failure
E16
Compressor phase interruption
abnormality
E17
Motor position detection
abnormality