MovinCool CM25 Service Manual User Manual
Page 60

Repair Section
60
< NOTE >
*1 Displayed in accordance with the WMC temperature unit setting.
Displayed
Code
Display Item
Display
Units
Display Example
01
Compressor speed
rps
90 (90 rps)
02
Electronic expansion valve position
pulse
3 50 (350 pulse)
03
Evaporator fan motor speed
rpm
8 80 (880 rpm)
04
Condenser fan motor speed
rpm
8 65 (865 rpm)
05
Compressor operating current
A
15 (15 A)
06
Evaporator inlet air thermistor (RTS2)
*1
°F/°C
80 (80°F)
07
Condenser inlet air thermistor (ODS)
*1
°F/°C
95 (95°F)
08
Condenser thermistor (CTS1)
*1
°F/°C
120 (120°F)
09
Evaporator pipe inlet thermistor (CTS2)
*1
°F/°C
104 (104°F)
10
Evaporator pipe outlet thermistor (CTS3)
*1
°F/°C
40 (40°F)
11
Self-diagnostic code
-
DF, IR, OR