beautypg.com

76 (1) relay board warning – MovinCool CM25 Service Manual User Manual

Page 76

background image

Repair Section

76

(1) Relay board

WARNING

• Do not touch the relay board until the green LED7 is turned off. Failure to follow this

warning may lead to electrical shock.

Removal of Relay Board

1) Disconnect the power at the source.

2) Loosen the bottom screw. (See page 69.)

3) Take out the nine (9) screws, and then remove the service panel. (See page 69.)

4) Disconnect all connectors from the relay board (18 connectors, 7 connections on the relay).

Refer to the figure “Relay board” to identify the relay connections and the connectors marked as

CN##. (To ensure easy reinstallation, be sure to label each connector wire as you remove them)

5) Take out the six (6) screws, and remove the relay board. The ground line for the relay board is

tightened together with the bottom right screw. (As shown in the illustration above, the relay

board and bracket assembly are replaced as a set.)

ILL00662-00

CN18

CN17

CN1

9

CN20

CN21

CN6

CN8

CN10

CN7

CN

9

CN1

1

CN5

LED1

LED2

LED3

LED4

LED5

LED6

CN12

CN13

CN14

CN4

CN2

CN3

CN1

CN106

CN107

to Output Signal

to Internal
Drain Pump Motor

to Electronic
Expansion Valve

to Wall Mounted
Controller

DIP Switch

to Condenser
Thermistor

to Condenser
Inlet Air
Thermistor (ODS)

to Condenser
Fan Motor

to Condenser
Fan Motor

to Noise Filter

Tighten Together

Ground Line

to Compressor

to Inductor Coil

to Evaporator
Fan Motor

LED 1~6

LED 7

to Evaporator
Fan Motor

to High-Pressure
Switch

to Compressor
Overlord Relay

to Float
Switch

to Stop
Switch

to Millivolt
Thermostat

to Evaporator
Inlet Air
Thermistor

to Evaporator Pipe
Inlet Thermistor and
Evaporator Outlet
Thermistor

CN103

CN101

CN102

CN104

CN105