6.3 Troubleshooting Chart

• To accurately troubleshoot the problem, it is important to carefully confirm the nature of the

problem.

• If conditions persist after the above actions have been taken, turn the unit off, disconnect the

power and contact your MovinCool reseller or a qualified technician.

• Self-diagnostic codes are not displayed for the MWT. To identify the cause, check the LED on

the relay board and refer to the charts on page 44 to 46.

Condition

Check Area

Possible Cause

Remedy

Unit does not operate.

LCD display turns off.

1. Voltage

Power failure.

Repair power supply.

Turn the circuit breaker on.

2. Ground fault breaker trip

Ground fault or defective

ground fault.

Repair ground fault section.

Reset or repair circuit

breaker.

3. Fuse

Fuse is blown.

Replace fuse on the relay

board.

4. WMC/MWT

Incorrect connection.

Connect the wires correctly.

DIP switch setting is

incorrect.

Correct DIP switch setting.

5. Stop switch

Stop switch is in the STOP

position.

Turn the stop switch to

OPERATE.