39 (2) dip switch configuration and setting – MovinCool CM25 Service Manual User Manual
Page 39

Operation Section
39
(2) DIP switch configuration and setting
• The controller of the unit is equipped with DIP switches that default in the OFF position. The DIP
switch can be set to configure the following functions.
Switch
Name
Switch
Number
Function
DSW1
1
ON
Enables the MWT.
OFF
Enables the WMC.
2
ON
No function.
OFF
DSW2
1
ON
Initializes setting of the condenser and evaporator fan motors after replacing the fan motors.
OFF
Set to OFF when the motor replacement is completed.
2
ON
No function.
OFF
DSW3
1
ON
Enters the test mode.
OFF
Exits the test mode.
2
ON
Disables the internal condensation removal pump.
OFF
Enables the internal condensation removal pump.
3
ON
No function.
OFF
4
ON
No function.
OFF
DSW4
1
ON
No function.
OFF
2
ON
OFF
3
ON
OFF
4
ON
OFF
I003192
ON
OFF
1
2
1
2
1
2
3
4
1
2
3
4
DSW1
DSW2
DSW3
DSW4