Operation Section

33

5.6 Warning Signal Connection (Output Signal Terminal L+ and L-)

• The unit is equipped with a warning signal output relay type (Form-C, normal open dry contact)

that can be used to monitor the failure condition.

• The relay contactor is closed when the following conditions have occurred:

- Condensation overflows

- Temperature sensor fails

- Cooling function fails

• The relay output contactor is rated 2 A at 30 VDC or 2 A at 30 VAC maximum with resistive load,

and is compatible with various warning devices such as alarm speakers, light indicators, etc.

< NOTE >

Use the recommended warning signal wire size from 16 AWG to 26 AWG for a solid wire, or 16

AWG to 22 AWG for a stranded wire.

• Connect the warning signal wires to terminal L+ and L- in the unit control box according to the

labels shown below.

ILL00286-00

L–

L+

E–

E+

G4

C4

P

RC

Y1

Y2

G

G1

Unit Terminal

Warning Device

Signal

Relay Output Contactor