beautypg.com

Metro Mobile Computing Workstations MPS-4007 Lithium Ion Nano-Phosphate Power Supply User Manual

Page 50

background image

50

Metro

TM

MPS-4007 Li-Nano Power Supply Operations Manual Supplement

InterMetro Industries Corporation

Warning 5:

Power Supply Low temperature

• System temperature below 0 °C (32 °F) has been detected. Ambient

temperature is below operating range, temperature sensor has failed or
has become disconnected.

• If power supply or its workstation are in an area where the temperature

is below 0 °C (32 °F - freezing), move to an area of ambient temperature
above 0 °C (32 °F - freezing), otherwise,

• Turn off computer equipment and then the power supply.
• Turn on the power supply and restart the computer equipment.

• If this problem continues, contact InterMetro Customer Service.

No Battery Warning
• No battery packs are detected in the power supply. Battery packs most

likely were not connected before the power supply was placed into
service.

Notice: The battery cells are not connected during shipment due to

USDOT AND IATA regulations.

• Turn off computer equipment and then the power supply.
• Make sure battery packs are connected by performing procedure in

“Connecting the Power Supply Batteries” above.

• Turn on the power supply and restart the computer equipment.
• If this problem continues, contact InterMetro Customer Service.

Warning 6:

Battery Pack Low temperature

• Pack temperature below 0 °C (32 °F) has been detected. Ambient

temperature is below operating range, temperature sensor has failed or
has become disconnected.

• If power supply or its workstation are in an area where the temperature

is below 0 °C (32 °F - freezing), move to an area of ambient temperature
above 0 °C (32 °F - freezing), otherwise,

• Turn off computer equipment and then the power supply

.

• Turn on the power supply and restart the computer equipment.
• If this problem continues, contact InterMetro Customer Service.

Warning 7:

Output fuse blown

• The DC output fuse is blown.
• Immediately turn off the power supply.
• Check your workstation cart for a possible short.

• Replace the fuse as specified in “Fuse replacement” above.
• Turn on the power supply and restart the computer equipment.

• If this problem continues, contact InterMetro Customer Service.